background image

Installation, Operation and Maintenance Manual

IO-70103  RevE  08-17

10

INSTALLATION INSTRUCTIONS

The ASCO SERIES 500 Surge Protective Devices (SPDs) are high quality, high energy surge current 
diversion systems designed to protect sensitive equipment from damaging transient voltage surges. 
Proper installation is required for maximum system performance.

The installer should perform the following steps to assure a quality installation. The entire installation 
manual should be read before starting installation. These instructions do not replace national or local 
electrical codes. Check applicable electrical codes to ensure compliance. Installation of the SPD system 
should only be performed by qualified personnel.

1.  Insure that all power is removed before beginning installation. A qualified licensed electrician shall 

install all electrical connections.

2.  The standard SPD is provided in a 520- NEMA 12 (Indoor), 515- NEMA 1 (indoor), 510- NEMA 4X rated 

enclosures. Verify the SPD enclosure rating by referencing position 14 in the model number.

3.  Determine where the SPD is to be mounted, allowing for minimum length of wire between itself and 

the input power terminals of the service panel. Punch or cut the proper hole size  in  the  side  of  the  
SPD  closest  to  the  knockout  to  be utilized in the service panel (plastic NEMA 4X “J” enclosure 
units include a flexible conduit/nipple accessory – no punching or drilling required in SPD). Drill 
mounting holes in wall at location picked for SPD next to service panel using mounting dimensions 
shown in the table below. Mount surge suppressor to wall using appropriate size & type hardware. 

4.  Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, 

and the green wire (ground) marked G, of the SPD using the wire range listed below. To yield the best 
performance of the SPD within the electrical distribution system, keep all conductors as short as 
possible and avoid sharp bends.

5.  Connection to the unit’s summary alarm contacts shall be with #18 – 22 AWG. The ratings of the Form 

‘C’ contacts are 5 amps at 250 VAC maximum with a power factor of 1.0. For additional information, 
see “Monitoring” section.

6.  Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and 

the front door of enclosure are illuminated. If the GREEN LEDs are extinguished or a RED LED is 
illuminated, check to ensure that power is applied to the SPD. If an abnormal indication is present, 
remove power to the SPD and contact ASCO Surge Protection at: 1-800-237-4567 or 1-727-535-6339.

7.  Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are 

extinguished or the RED LED is illuminated. Please contact ASCO Surge Protection at: 1-800-237-
4567 or 1-727-535-6339.

8.  The protection modules in these SPDs may be replaceable, contact ASCO Surge Protection for 

replacement.

NOTICE - If the SPD model is configured to include a neutral connection (“Y”, “H”, “S”, “N”), and a Neutral 
connection is not available, please contact factory.

Summary of Contents for 510

Page 1: ...Surge Protective Devices Installation Operation Manual Model 520 Model 515 Model 510 Model 520 Model 515 Model 510 ...

Page 2: ...n NEC Considerations Voltage Protection Rating Circuit Ampacity Limitations System Grounding and Bonding Grounding Electrode Neutral Connection Parallel Connection Wire Diagram 6 6 6 6 7 7 7 7 7 7 MONITORING FEATURES External Status Indicators Standard Audible Alarm Standard Optional Summary Alarm Contact Standard Optional Transient Counter Optional 6 6 6 6 UNPACKING AND INSTALLATION Unpacking and...

Page 3: ...ctronic appliances solid state motor drives etc For interconnected electronic loads such as by way of data cabling transient surge suppression should also be applied to the interconnecting wiring data cables Environment Unit is designed for operation indoors in ambient temperatures of 0ºC 32ºF to 40ºC 104ºF with a relative humidity of 0 to 95 non condensing The unit is provided in an industrial us...

Page 4: ...E THIS SYSTEM ELECTRICAL SAFETY PRE CAUTIONS MUST BE FOLLOWED WHEN INSTALLING OR SERVICING THIS EQUIPMENT TO PREVENT RISK OF ELECTRICAL SHOCK TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE MAKING ELECTRICAL CONNECTIONS OR SERVICING DANGER SEULEMENTLEPERSONNELQUALIFIÉDOITINSTALLEROUMAINTENIRCESYSTÈME DES PRÉCAUTIONS DE SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE SUIVIS LORS DE L INSTALLATION O...

Page 5: ...Option X Yes Trailing Accessory Option Common Systems 120S 240 120V Split Phase 1Ø 3W Grnd Fig 1 120Y 208Y 120V Wye 3Ø 4W Grnd Fig 2 240H 240 120V High Leg Delta B High Fig 3 277Y 480Y 277V Wye 3Ø 4W Grnd Fig 2 480D 480V Delta 3Ø 3W Grnd Fig4 HRG Wye Other Available Systems Confirmation Encouraged 120N 120V Single Phase Fig 5 127N 127V Single Phase Fig 5 127S 254 127V Split Phase 1Ø 3W Grnd Fig 1 ...

Page 6: ...Grnd Fig 2 230N 230V Single Phase Fig 5 240N 240V Single Phase Fig 5 Not split phase 240Y 415Y 240V Wye 3Ø 4W Grnd Fig 2 240C 240V B Corner Grnd Delta 3Ø 3W Grnd Fig 6 240D 240V Delta 3Ø 3W Grnd Fig 4 254N 254V Single Phase Fig 5 254Y 440Y 250V Wye 3Ø 4W Grnd Fig 2 277N 277V Single Phase Fig 5 277S 480 240V Split Phase or Two legs of Wye Call 480H 480 240V High Leg Delta B High Fig 3 Voltage Codes...

Page 7: ...e 240Y 415Y 240V Wye 3Ø 4W Grnd Fig 2 240C 240V B Corner Grnd Delta 3Ø 3W Grnd Fig 6 240D 240V Delta 3Ø 3W Grnd Fig 4 254N 254V Single Phase Fig 5 254Y 440Y 250V Wye 3Ø 4W Grnd Fig 2 277N 277V Single Phase Fig 5 277S 480 240V Split Phase or Two legs of Wye Call 400D 300V Single Phase Fig 5 415D 415V Delta 3Ø 3W Grnd Fig 4 480C 480V B Corner Grnd Delta 3Ø 3W Grnd Fig 6 480H 480 240V High Leg Delta ...

Page 8: ...tandard 1449 Fourth Edition System Grounding and Bonding The performance and safety of any SPD system is dependent on proper grounding and bonding Grounding is required for safety Correct implementation also enhances equipment performance Incorrect grounding can reduce or impede the SPD s operation All electrical circuits to the SPD must include an equipment grounding conductor as required by the ...

Page 9: ...s the surge current to the grounding electrode earth connection However for most transient surges that are developed by switching loads the SPD diverts the surge current back to its source without involving the grounding electrode For proper SPD performance the service entrance grounding electrode system must comply with the NEC by having all available electrodes building steel metal water pipe dr...

Page 10: ...ing required in SPD Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimensions shown in the table below Mount surge suppressor to wall using appropriate size type hardware 4 Connect black wires line or phase marked L1 A L2 B or L3 C the white wire neutral marked N and the green wire ground marked G of the SPD using the wire range listed below To yield t...

Page 11: ...2 lb 14 5 kg 200 320 41 lb 18 6 kg 400kA 500kA 20 x 16 x 8 508 x 406 x 203 21 25 539 8 20 508 0 44 11 2 56 lb 25 4 kg MODEL 510 Suggested Circuit Breaker And Wire Size B E 1 35 34 03 D A C F Summary Alarm Contacts Connection shall be with 18 22 AWG Form C contacts are rated 5 amps at 250 VAC max Overcurrent Protection Circuit Breaker Allowable Range 15A 30A Suggested Size 30A Connection Wire Allow...

Page 12: ...able Range 14 2 Suggested Size 10 Weight 30 lb 13 6 kg Summary Alarm Contacts Connection shall be with 18 22 AWG Form C contacts are rated 5 amps at 250 VAC max DIMENSIONAL INFORMATION A 18 457 B 12 305 C 6 152 D 11 279 E 15 381 F 20 25 514 G 21 5 546 515 SPD Panelboard Extension Customer Supplied Panelboard A G FLUSH F SURFACE E B D C With AC Applied NC Normally Open COM Common NO Normally Closed...

Page 13: ...s all surges that deviate from the line sine wave The factory setting is 30 over nominal line voltage Other settings include 50 70 and 100 TROUBLESHOOTING SERVICING MAINTENANCE Troubleshooting If status failure indication occurs or summary alarm contacts have changed state a qualified electrician shall first determine if the systems voltage and proper phasing exists If the SPD remains in an alarm ...

Page 14: ...e and replaced if necessary Standard electrical trouble shooting procedures should be used to isolate problems other than failed surge current diverter modules When replacing components use identically rated components for continued proper operation and safety Please contact factory for information on replacement parts Preventative Maintenance Inspection and Cleaning Periodic system inspections cl...

Page 15: ...Installation Operation and Maintenance Manual IO 70103 RevE 08 17 15 ...

Page 16: ...ile every precaution has been taken to ensure accuracy and completeness in this literature ASCO assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions The ASCO and ASCO Power Technologies marks are owned by Emerson Electric Co or its ailiates and utilized herein under license 2017 ASCO Power Technologies All Rights Re...

Reviews: