ASCO 430 Surge Protective Device (SPD)
Electrical
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Confirm the surge protective device voltage rating on the module or
nameplate label is not less than the operating voltage.
Failure to follow these instructions will result in death or serious injury.
Prior to mounting the SPD, verify that the device has the same voltage
rating as the power distribution system in which it is installed. Compare the
nameplate voltage or model number on the SPD with the nameplate of the
electrical distribution equipment.
The specifier or user of the device should be familiar with the configuration
and arrangement of the power distribution system in which the SPD is to be
installed. The system configuration of any power distribution system is based
strictly on how the secondary windings of the transformer supplying the ser-
vice entrance main or load are configured. This includes whether or not the
transformer windings are referenced to earth via a grounding conductor. The
system configuration is not based on how any specific load or equipment
is connected to a particular power distribution system. See Table 1 for the
service voltage of each SPD.
Electrical
Voltage Rating
Table 1:
Model 430 Service Voltages
DANGER
Voltage Codes
P
C
J
A
Per Phase
kA Rating
System
Modes of
Protection
(Default)
Connection
Type
Monitoring
Options
Enclosure
UL 1449
Type1/Type 2
0
Option(s)
kA Rating
Per Phase
430
Model 430
Product Line
J = NEMA 4X Non-Metallic
(Polycarbonate)
Size - 6” x 6” x 4”
C = Compression
Lugs
S = LEDs
A = LEDs/Audible Alarm/Relay
1 = UL 1449 Type 1
2 = UL 1449 Type 2,
(Includes UL1283
Filter)
10 = 100kA
15 = 150kA
20 = 200kA
120S = 120/240V Split Phase - 1Ø, 3W+Grnd
120Y = 208Y/120V Wye - 3Ø 4W+Grnd
240H = 240/120V High Leg Delta (B High)
277Y = 480Y/277V Wye - 3Ø 4W+Grnd
347Y = 600Y/347V Wye - 3Ø 4W+Grnd
480D = 480V Delta - 3Ø 3W+Grnd & HRG Wye
120N = 120V Single Phase
127N = 127V Single Phase
127S = 127/254V Split Phase - 1Ø 3W+Grnd
127Y = 220Y/127V Wye - 3Ø 4W+Grnd
220Y = 380Y/220V Wye - 3Ø 4W+Grnd
230Y = 400Y/230V Wye - 3Ø 4W+Grnd
240N = 240V Single Phase - Not split phase
240S = 240/480V Split Phase - 1Ø, 3W+Grnd
240Y = 415Y/240V Wye - 3Ø 4W+Grnd
240C = 240V B Corner Grnd Delta, 3Ø 3W+Grnd
240D = 240V Delta - 3Ø 3W+Grnd
254Y = 440Y/254V Wye - 3Ø 4W+Grnd
277N = 277V Single Phase
300N = 300V Single Phase
300Y = 520Y/300V Wye - 3Ø 4W+Grnd
480N = 480V Single Phase (1 Hot, 1 Neu, 1 Grnd)
480C = 480V B Corner Grnd Delta, 3Ø 3W+Grnd
600C = 600V B Corner Grnd Delta, 3Ø 3W+Grnd
600D = 600V Delta - 3Ø 3W+Grnd & HRG Wye