background image

© 2020 ASCO Power Technologies. All Rights Reserved

For troubleshooting, call technical assistance at 1-800-237-4567 or [email protected]

5

IO-70061

01/2020

ASCO 430 Surge Protective Device (SPD)

Precautions

Precautions

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Apply appropriate personal protective equipment (PPE) and follow safe 

electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462.

• 

This equipment must only be installed and serviced by qualified electri

-

cal personnel.

• 

Turn off all power supplying this equipment before working on or inside 

equipment.

• 

Always use a properly rated voltage sensing device to confirm power is off.

•  Replace all devices, doors and covers before turning on power to this 

equipment.

• 

This equipment must be effectively grounded per all applicable codes. 

Use an equipment-grounding conductor to connect this equipment to the 

power system ground.

Failure to follow these instructions will result in death or serious injury.

WARNING:

 This product can expose you to chemicals including 

DINP, which is known to the State of California to cause cancer, and 

DIDP which is known to the State of California to cause birth defects 

or other reproductive harm. For more information go to: www.

P65Warnings.ca.gov.

NOTICE

LOSS OF BRANCH CIRCUIT POWER / LOSS OF SURGE 

SUPPRESSION

•  Perform periodic inspection of the surge protective device status 

indicator lights as part of the preventative maintenance schedule.

•  Promptly replace the surge protective device when an alarm state 

exists.

•  Use dry contacts to signal an alarm state to the central supervisory 

system for unmanned, inaccessible, or critical installations.

•  Use multiple surge protective devices to achieve redundancy for critical 

applications.

Failure to follow these instructions can result in equipment damage.

At end-of-life conditions, Surge Protective Devices (SPDs) can lose their 

ability to suppress power system transient voltage spikes and attempt to 

draw excessive current from the line. This SPD is equipped with overcurrent 

and overtemperature components that will automatically disconnect the 

surge suppression elements from the mains should the surge suppression 

elements reach end of life. Tripping of the branch circuit breaker or fuse 

feeding the SPD can occur. Mitigate the tripping of the branch circuit breaker 

or fuse feeding the SPD by coordinating the surge suppression elements 

with the branch circuits.

DANGER

Summary of Contents for 430

Page 1: ...Surge Protective Devices Installation Operation Manual Model 430 ...

Page 2: ... 2020 ASCO Power Technologies All Rights Reserved For troubleshooting call technical assistance at 1 800 237 4567 or customercare ascopower com 2 IO 70061 01 2020 ...

Page 3: ...Noise Mounting Service Clearance Equipment Performance Electrical Voltage Rating Branch Circuit Overcurrent Protection and Disconnect Means Location of Surge Protective Device SPD System Grounding Wiring ASCO 430 Wiring Diagrams Installation Surface Mount Installation Flush Mount Installation Operation LED Status Indicators Audible Alarm Dry Contacts Remote Monitor Option Preventive Maintenance 3 ...

Page 4: ...nal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situation which if not avoided could result i...

Page 5: ... is known to the State of California to cause birth defects or other reproductive harm For more information go to www P65Warnings ca gov NOTICE LOSS OF BRANCH CIRCUIT POWER LOSS OF SURGE SUPPRESSION Perform periodic inspection of the surge protective device status indicator lights as part of the preventative maintenance schedule Promptly replace the surge protective device when an alarm state exis...

Page 6: ... STPS or CSA Z462 This equipment must only be installed and serviced by qualified electrical personnel Turn off all power supplying this equipment before working on or inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicabl...

Page 7: ...relative humidity of 0 to 95 non condensing This device has a Type 4X housing The device background noise is negligible and does not restrict the location of the installation The device has been designed to be surface mounted An additional flush mount kit is also available if required KITFMXF or stainless steel flush mount kit KITFMXFSS The service clearance should meet all applicable code require...

Page 8: ...how any specific load or equipment is connected to a particular power distribution system See Table 1 for the service voltage of each SPD Electrical Voltage Rating Table 1 Model 430 Service Voltages DANGER Voltage Codes P C J A Per Phase kA Rating System Modes of Protection Default Connection Type Monitoring Options Enclosure UL 1449 Type1 Type 2 0 Option s kA Rating Per Phase 430 Model 430 Produc...

Page 9: ... ASCO 430 device per applicable state and local building codes UL 1449 Type 1 SPDs have been designed and approved for line side appli cations prior to the main service disconnect without supplemental overcur rent protection Type 2 SPDs must be installed on the load side of the main Overcurrent Protective Device OCPD All installations should either provide or include a disconnecting means Type 1 S...

Page 10: ...tions will result in death or serious injury NOTICE LOSS OF SURGE SUPPRESSION Verify that the service entrance equipment is bonded to ground in accordance with all applicable codes Failure to follow these instructions can result in equipment damage The ASCO 430 has SPD elements connected from phase to ground It is critical that there be a robust and effective connection to the building grounding s...

Page 11: ...rehensive electrical maintenance program Failure to follow these instructions can result in equipment damage HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Apply appropriate personal protective equipment PPE and follow safe electrical work practices See NFPA 70E NOM 029 STPS or CSA Z462 This equipment must only be installed and serviced by qualified electri cal personnel Turn off all power supply...

Page 12: ...ry twelve inches of length 6 Do not loop or coil wires Be sure to maintain adequate wire bending space per NEC 7 Use on solidly grounded systems unless the SPD model is designed for installation on ungrounded HRG systems HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH For outdoor installation use and appropriate weather sealing at the nipple o ring sealing conduit etc Failure to follow these instr...

Page 13: ... Installation Figure 7 Single Phase Two Wire Ground V Neutral White Phase A Black Ground Green CONTACTS NO C NC DRY SERVICE A C B N G Installation Operation and Maintenance Manual IO 70061 RevJ 09 18 A B C G N BREAKER Use closest breaker to SPD Locate SPD close to intended breaker Keep Leads Short as Possible Avoid Sharp Bends Rotate Model 430 such that LED indicator is most visible Outdoor instal...

Page 14: ...ng Note 1 The neutral conductor is not present on three wire Wye grounded power systems For improved operation of the SPD bond the neutral and ground lugs together inside the SPD Phase A Black Phase C Black Ground Green V CONTACTS NO C NC DRY SERVICE A C TWO POLE A C G HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH The high leg of the power system must connect to the B phase lug of the SPD Failur...

Page 15: ...nside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicable codes Use an equipment grounding conductor to connect this equipment to the power system ground Failure to follow these instructions will result in death or serious in...

Page 16: ... the unit will be supported from its back 3 Configure the electrical conductor and conduit connection consistent with the installation instructions on pages 9 through 13 Preplan connections such that they are completed prior to fastening the unit to the backing plate 4 Install faceplate cover applying a torque of 5 lb in 0 5 N m to the four screws prior to energizing and testing the unit Flush Mou...

Page 17: ...and Audible alarm ON Loss of surge suppresion Indicator light ON red loss of surge suppresion The audible alarm does not have a silence switch Silence the alarm by removing power from the SPD The alarm indicates that the device needs replacement by qualified electrical personnel INADEQUATE DRY CONTACT USE Do not supply more than 24 Vdc 24 Vac and no more than a current of 2 A Failure to follow the...

Page 18: ...d an audible alarm with an enable disable switch Normal status is a lit green LED and no audible alarm To test the integrity of the remote monitor press the push to test switch The green LED will turn off the red LED will turn on and the alarm will sound if the alarm is enabled Releasing the switch will complete the test the red LED will turn off the green LED will turn on and the alarm will shut ...

Page 19: ...his equipment must only be installed and serviced by qualified electri cal personnel Turn off all power supplying this equipment before working on or inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicable codes Use an equ...

Page 20: ...nd completeness in this literature Schneider Electric assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 14550 58th Street North Clearwater Florida 33760 se com us en work support 1 888 778 2733 ...

Reviews: