18 Chapter 3 Maintenance and Troubleshooting
ASCO Series 230 C2ADTL Transfer Switch User Manual
Once you, successfully set up the manual control mode,
the “Auto” LED on the controller panel will blink.
(1) Electric Operation Test
The transfer switch can now transfer and return. The operation should be smooth. Description of the operation is
as follows.
7. Manu Control
Manu Action
7.1 Switch Ctrl
Action
7.1 Switch Ctrl
X->II
Enter
Up
Down
Enter
Up
Down
Enter
Up
Down
Menu
Operation
Description
Manu Control
Scrolling the main menu to
“Manu Control” ,and press
“Enter” button.
Switch Ctrl
Next,Scrolling the menu to
“Switch Control” ,and press
“Enter” button.
Switch Ctrl
Then Scrolling the menu to the
target location,such as the
transfer switch is in location
I,scrolling the menu to “X
→
II”
and press “Enter” button,the
switch should be transferred to
Location II.
Operate the switch again,it can be
tansferred to Location I,Location
OFF or Location II.If the switch is in
Location I,scrolling the menu to “X
→
I” and press Enter,the switch will not
tranfer.
(2) Return To The Original Control Mode
After completing the electric operation test, you can return to the original control mode by using the menu
settings.
Using C1000 Controller:
(1) According to The 230 Series Automatic Transfer Switch C1000 Intelligent Controller User Manual, the
DIP 7-
8 is set to ON, ON, the run LED will blink, and one of the switch’s Position Indication LED’s will
blink, The controller is now in manual control mode.
(2) The blinking LED is the target position that the switch will transfer to. Press the key less than 3 seconds, the
position indication LED will blink alternately to show which position is target transfer. Choose a transfer target
position.
(3) Press the key 3 Sec, and the switch will transfer to the target position.
(4) The switch can transfer and return by this method, and the operation should be smooth.
(5) According to The 230 Series Automatic Transfer Switch C1000 Intelligent Controller User Manual, the DIP 7-8
is set to automatic or remote Mode, and the controller will exit manual control mode.