IO-70067
01/2020
ASCO 360 Surge Protective Device (SPD)
Operation
Operation
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462.
•
This equipment must only be installed and serviced by qualified
electrical personnel.
•
Turn off all power supplying this equipment before working on or inside
equipment.
•
Always use a properly rated voltage sensing device to confirm power is
off.
• Replace all devices, doors and covers before turning on power to this
equipment.
•
This equipment must be effectively grounded per all applicable codes.
Use an equipment-grounding conductor to connect this equipment to the
power system ground.
Failure to follow these instructions will result in death or serious injury.
DANGER
LED Status Indicators
Diagnostic LEDs are located on the front of the ASCO 360 SPD device.
They operate as follows:
• Verify that all phase voltages are present. If any of the LEDs are not
illuminated, the device may not be installed correctly. Check the power
supply and service voltage. Upon energizing the SPD, check the LED status.
• If all of the LEDs are illuminated, surge suppression is operating.
• If one or more LEDs are not illuminated, there is a loss of surge
suppression on that phase.
•
If an inoperative condition occurs the device must be replaced by qualified
electrical personnel.
Light 1
Light 2
Corrective Action
Out
Out
Check Power Supply
Before Replacing Unit
Green
Green
No action
Out
Green
Replace Unit
Green
Out
Replace Unit
Note:
Single phase units will only have one light, 2 light configuration is for
split phase units only.