12.

 

Press the PROGRAM button 

once more 

to set the day and time for ending the 

exercise.  A default time AM 12:00 appears in the display.  A small 2 appears to 
the right of the time.  The lamp symbol is absent.  The 2 (or even number) 
indicates the end of an exercise or open contacts.  The absence of the lamp symbol 
indicates when the exerciser contacts will open.

 

 
13.

 

Press the DAY button repeatedly until an arrow appears under the desired day for 
terminating the exercise (Monday = 1) as in step 9.

 

 
14.

 

Press the MINUTE button repeatedly until the desired minute of the exercise 
termination hour is displayed, such as AM 5:40 or PM 5:40.

 

 
15.

 

Move the slider on the SET switch to the "run" position.  The exerciser time clock 
is now programmed to start the emergency generator at the desired day, time and 
for the desired duration.

 

 
 
 

NOTE:

 

It is possible to program one to eight "on - off" cycles or transitions for the 

following day combinations: One to eight "on-off" cycles any day of the week; One to 
eight "on-off" cycles Monday to Friday inclusive; One to eight "on-off" cycles both 
Friday and Saturday only; One to eight "on-off" cycles Monday to Saturday inclusive; 
One to eight "on-off" cycles Monday to Sunday inclusive; All day combinations can have 
any combination of  "on -off " cycles

. Normally the exerciser time clock will only 

require one "on-off" cycle once per week.

  The programming steps given above describe 

how to exercise the generator once a week.  

EXAMPLE

:

 Suppose that the desirable day 

and time for exercising the generator is Saturday at 5:00 AM.  Move the slider of the 

SET 

SWITCH

 to the right (P in circle) position. Press the 

DAY BUTTON

 (1..7) repeatedly until 

the arrow appears under day 6.  Press the 

HOUR BUTTON

 (h) followed by the 

MINUTE 

BUTTON

 repeatedly until the desired time

 

AM

5: 30 are displayed.  The generator is to be 

shut down after exercising for 10 minutes.  With the slider of the 

SET SWITCH

 still in the 

right (P in circle) position press the PROGRAM BUTTON 

once

.  The display will show 

a continuous default time of  

AM

 12:00.  The day arrow(s) disappears.  The small 1 will 

change to a 2 and the lamp symbol disappears.  Press the DAY BUTTON (1..7)  again 
repeatedly until the day arrow appears under day 6. Press the 

HOUR BUTTON

 (h) followed 

by the 

MINUTE BUTTON

 again repeatedly until the desired time 

AM

5: 40 are displayed.  

Return the 

SET SWITCH

 slider to the "run" position.  The exerciser time clock is 

programmed to start the generator at 5:30 AM on Saturday morning and run for 10 
minutes then shut down at 5:40 AM of the same day Saturday.  Following this procedure, 
the generator can be exercised as frequently as desired.  

 

 