Electrical connections  

The  power  supply  has  to  be  connected  to 

  and 

  is  considered  as  system  ground.  The 

same ground reference has to be used for the aSENSE VAV unit and for any connected device!  Unless 
different transformers are used, special precautions need to be taken. 
 
NOTE! 
The signal ground is not galvanically separated from the aSENSE VAV power supply! 

 

NOTE! 
The same ground reference has to be used for the aSENSE VAV unit and for any connected device! 

 

If possible keep the sensor powered up after mounting. Connect the analogue output before 
measuring.  

Connection 

Terminal 

Function 

Electrical Data 

Remarks 

 

 

 

Power (+) 

 

Power ground (-) 

24 VAC/DC+  (+-20%), 3W 

 

24 VAC/DC- 

2W without output load 
See note 1! 

Out(1) 

 

 
 

Out(2) 

 

 
 

Analogue Output 1 (+) 

 
 
 

Analogue Output 2 (+) 

 
 
 

Signal Ground (-) 

0

─10 VDC or 0─20 mA, 

2

─10 VDC or  4─20 mA,

 

 
 

Same as Output 1 

 
 

Connected to 

 via PTC 

fuse 

According to positions of 
Out(1) jumper and start 
point selection. See note 2! 
 
According to positions of 
Out(2) jumper and start 
point selection. See note 2! 
 
See note 1! 

 

 

Normally open relay 

Contact free relay 

minimum load 1mA/5V  

rated load 0.5A/125VAC; 

1A/24VDC 

Triggered by register Out(3) 

Out(4) 

 

Analogue Output 4 (+) 

 

or Open Collector 

0-10 VDC 

 

Max 0.5A, 55VDC / 40VAC        

(half-wave rectifier protection) 

According to positions of 
Out(4).  
See note 2 and 3! 

DI1  

 

DI1 

Digital Input 1 

Closed contact current 1mA 

Open contact voltage max 5V 

Do not apply any voltage 
on this input! 

Table I.  Electrical terminal connections for aSENSE

 

VAV 

 

Note 1: 

  The ground terminal is used as negative power supply DC input or AC phase ground 

 

(half wave rectifier). The signal ground M, protected by a PTC resistor, is the same as power ground 

 

(permitting a ”3-wire” configuration). A single transformer may be used for the entire system.  

 
Note 2:

   aSENSE  VAV can deliver both a voltage or a current loop for  Out(1) / Out(2). For Out(4) a 

voltage output or an open collector output is selected with jumper OUT4. To change between voltage 
and current output mode the hardware jumpers are used. There is one jumper for  Out(1) and one for 
Out(2), so that one output can be a voltage output and the other a current output. Both, voltage output 
and  current  output,  can  have  start  points  0  %  (0

─10  VDC  or  0─20mA)  or  20%  (2─10  VDC  or 

4

─20mA) selected from PC software.  

 

Note 3:

  Current of Open Collector is internally returned to 