Artistic License Dali-Scope User Manual Download Page 6

Page 6 

DALI-Scope User Guide

 

y

PRESET: [CHANNEL / GROUP] – Preset 

memory for either channel or group
 -

UP  or  DOWN  used  to  select  value  (0- 

100%)

 -LEFT or RIGHT used to select index
 -LEFT (hold) then RIGHT used to select 

between channel or group

  

Note: These presets are held in 

memory.

STATUS

ADDRESS

Use the STATUS button to scroll through the 

different sub menus below:

 

y

DALI  BUS  POWER:  [OK/DALI  PSU 

PRESENT/NO PSU PRESENT]

 

y

BALLAST  STATUS:  [OK/ERR/NOT 

PRESENT]

 

y

LAMP  STATUS:  [OK/FAILURE/NOT 

PRESENT]

 

y

LAMP POWER: [ON/OFF/NOT PRESENT]

 

y

RESET STATE: [YES/NO/NOT PRESENT]

 

y

LIMIT ERROR: [YES/NO/NOT PRESENT]

 

y

VERSION NUMBER: [VERSION/

UNKNOWN/NOT PRESENT]

 

y

SHORT ADDRESS: [ADDRESS/

MISSING/NOT PRESENT]

 

y

CHANNEL ASSIGN: Used to change the 

channel assignment of a ballast
 -LEFT or RIGHT to select ballast to 

program

 -

UP or DOWN to select the new channel 

index

 -YES (and hold) to program ballast
 -NO to cancel new channel index (before 

programming occurs)

 

y

GROUP ASSIGN: Used to assign a ballast 

to a group
 -LEFT or RIGHT to select ballast to 

program

 -

UP or DOWN to select the new group

 -

YES (and hold) to confirm action

 -NO to cancel action (before programming 

occurs)

 

y

GROUP REMOVE: Remove a group 

assignment from a ballast
 -LEFT or RIGHT to select ballast to 

program

 -

UP  or  DOWN  to  select  the  group 

assignment that is to be removed

 -

YES (and hold) to confirm action

 -NO to cancel action (before programming 

occurs)

 

y

SCENE ASSIGN: Store a value for a 

scene within the ballast memory
 -LEFT or RIGHT to select ballast to 

program

 -

UP or DOWN to change the scene level

 -LEFT & RIGHT to select scene index
 -

YES (and hold) to confirm action

 -NO to cancel action (before programming 

occurs)

 

y

SCENE REMOVE: Remove a scene value 

from the ballast memory
 -LEFT or RIGHT to select ballast 
 -

UP or DOWN to change the scene that is 

to be removed

 -

YES (and hold) to confirm action

 -NO to cancel action (before programming 

occurs)

 

y

AUTO CHANNEL ASSIGNMENT: Assign 

short addresses to new ballasts
 -

YES (and hold) to confirm action

Note: This function is for programming new 

ballasts that have not been assigned a channel 

number. It will reset ALL ballasts on the DALI 

circuit and give them new channel numbers. If 

you need to program a new ballast on a circuit 

without affecting other ballasts, please isolate 

the new ballast.

Summary of Contents for Dali-Scope

Page 1: ...Dali Scope User Guide Artistic Licence Version 1 8 Dali Scope User Guide ...

Page 2: ...s before using the product Copyright Artistic Licence Engineering Ltd All rights reserved Download the user guide by scanning the following QR code WARNING Please ensure batteries are inserted with correct polarity failure to do so can result in product damage ...

Page 3: ... scrolls to show more information Test is used to transmit levels to ballasts Includes channel and group preset Address is used to configure the ballast with channel and group assignments Config is used to change ballast properties and Dali Scope configuration parameters Status reports ballast properties such as Lamp Status Reset State Short Address Ballast 1 Ballast 2 Ballast 3 Ballast 4 Ballast ...

Page 4: ...s enabling commercial lighting to become more efficient While the initial development focused on fluorescent ballasts applications now encompass a range of devices such as LED drivers HID and low voltage halogen In the future the scope will include rotaries light sensors and more DALI stands for Digital Addressable Lighting Interface It is technically managed under IEC 62386 System Commissioning A...

Page 5: ... DALI Bus PSU is present such as a Rail PSU D4 Note Only one controller should be present on the DALI circuit at any time When using the READ menu options Dali Scope does not transmit data messages so can be added to the DALI circuit at the same time as a DALI controller READ TEST There are 3 options available y y CURRENT VALUE Displays the value of the command or level that is transmitted by the ...

Page 6: ... or DOWN to select the new group YES and hold to confirm action NO to cancel action before programming occurs y y GROUP REMOVE Remove a group assignment from a ballast LEFT or RIGHT to select ballast to program UP or DOWN to select the group assignment that is to be removed YES and hold to confirm action NO to cancel action before programming occurs y y SCENE ASSIGN Store a value for a scene withi...

Page 7: ...llast UP or DOWN to select value YES and hold to confirm change NO to cancel request y y FAILURE LEVEL The level the ballast uses in case of DALI failure LEFT or RIGHT to select ballast Note Dali Scope does not allow this value to be changed y y FADE RATE The ballast fade rate as set in the DALI specification LEFT or RIGHT to select ballast UP or DOWN to select value YES and hold to confirm change...

Page 8: ...return to us User Interface Indication Connections RCA Jack phono DALI connection 1 no AA Battery compartment 1 no Configuration Set up menu option User Interface 9 button control panel Indication Dot Matrix display Control Control over 1 DALI circuit Output Protocols DALI Isolation Protection Isolation Opto Isolation on all DALI lines Package Contents Dali Scope User Guide Phono to Clip Lead 2x A...

Reviews: