12
o
Colour Type 1. Colour Temperature. Defines the 16-bit colour temperature based on
the black body line. Units are Mireks (1,000,000/K). 4000k cool white is
approximately 250 Mireks.
•
2 PRI-0
•
2 PRI-1
•
2 PRI-2
•
2 PRI-3
•
2 PRI-4
•
2 PRI-5
o
Colour Type 2. Primary N allows 8-bit control over up to 6 primary channels number
0 to 5.
•
3 RED
•
3 GREEN
•
3 BLUE
•
3 WHITE
•
3 AMBER
•
3 FREE
o
Colour Type 3. RGBWAF allows 8-bit control over red, green, blue, white, amber and
free (that is manufacturer defined) colour.
To change the colour type parameter, either select the field and use the UP and DOWN keys or press
FUNCT.
The next option field selects the address of the DALI device to be set. The UP and DOWN keys select:
•
Broadcast
–
send the commands to all devices.
•
GROUP
–
send the command to one of the 16 possible groups.
•
CHANNEL
–
send the command to one of the 64 possible channels.
The final option field is the value to which the colour parameter will be set. The colour parameters
vary between 8-bit and 16-bit. Data is entered in decimal so the field width varies between 3 digits
(0-255) and 5 digits (0-65535).
When channel addressing is used, Commissioner will read the data from the device, allowing the
user to edit the existing value.
During this process, the value field changes to ‘???’ while waiting for
the device to respond. If the value field remains in this display, the addressed device did not
respond.
To send the command, press ENTER.
Example
The following command will set all the DT8 devices in group 7 to a colour temperature of 250
Mireks.
Send DT8
1 TEMPc
to
GROUP 07
at
00250