FIREPLACE
| NEAT 70/80/90
8 |
Page
must be at least 35 cm
(Pic. 6.1.1)
.
For non flammable material, no requirements apply.
6.2.
Wooden beams protection
Given its properties, heat is transmitted through radiation. In case there are any wooden beams inside the radiation zone or in the way of the
hot air, they MUST be properly insulated because the continuous exposure in high temperatures can make them deteriorate faster or even
cause self ignition. Use proper insulation materials that are in accordance with European rules or, in case of high thermal stress you can also
use metal linings.
6.3.
General security instructions
Never leave children alone or without supervision near the fireplace when it is lit.
Teach children how to operate the fireplace correctly and safely.
Never touch the external surfaces of the fireplace or the glass when it is lit. There is a high risk of burns!
Due to the self closing door, you have to be extra careful when you are filling the fireplace.
It is forbidden to use the fireplace as a waste incinerator.
Don’t use burned or used wood as fuel.
Remove the ash only after it has completely cooled off.
Ash should be placed outdoors or be disposed in a place where there is no risk of ignition.
Immediately inform your specialized local supplier if you find any malfunction.
Don’t use chemicals or liquids as fire starters.
Do not use ANY fuel other than the recommended
6.4.
Flue security instructions
Prior to installing the ARTE® fireplace the chimney sweep or a qualified technician should check the condition and operation of your chimney
in accordance with the standards
EN13384-1
&
EN13384-2
.
This way you ensure the best conditions for heating without issues.
6.4.1.
Basic requirements for proper flue operation
The internal section of the flue must preferably be circular. In a case of square or rectangular
flue, the internal corners should have a radius of at least 20mm. In case of rectangular flue, the
ratio of the sides should be at maximum 1: 1.5
The flue must be properly insulated and waterproof and constructed of materials with thermal
resistance and resistance to combustion products and any deposits.
The flue must have no constrictions; it must have a vertical path and it should not change in
direction that exceeds 45
o
.
(Pic. 6.4.1.1)
In case of an existing flue the construction material should be checked. Materials such as
cement with lime, galvanized steel and rough or porous materials are contraindicated as they
Pic. 6.1.1
Pic. 6.1.2
Follow the operating instructions supplied with the product to help prevent fire and
protect the environment.