9
In this window
it is possible to change the ‘weight’ parameter for each input in relation to the
photovoltaic panels supplied, by pressing the relative ‘%’ key located beneath each reading.
For example: if inputs 1, 2, 3, 5, 6, 7 and 8 have a rated current of 180 A while input 4 has a rated
current of 140 A, the relevant settings are:
%1
= 100% -
%2
= 100% -
%3
= 100% -
%5
= 100% -
%6
= 100% -
%7
= 100% -
%8
= 100%;
%4
= 140/180*100 = 77.7
78%
See the next screen.
Press the ‘%’ key to access the following screen where the weight of the single string (in this example,
78) can be set through the + /
– buttons.
NOTE:
in the event that not all of the 8 inputs are used, the free input reading must be deactivated. Press the
‘%’ key corresponding to the free input and set the ‘weight’ to zero.