background image

 

Commissioning 

 

Fill the system by introducing water to both primary and 

secondary circuits in turn, all pipework vents should be 

open to allow air to escape freely. Ensure all air is 

removed from pump/s by venting pump casing. 

 

 

     

NOTE:

  Never run pumps dry. 

 

P.I.D. Digital Controller 

 

Set desired water temperature (normally 60

?

C by 

pressing the F key, this will cause the upper display to 

show set point and lower display will read SP, press the 

raise/lower keys to set desired temperature, press the F 

key once more to return to the normal display. If there is 

no key activity within 1 minute the display will 

automatically return to normal. Units with dual set point 

facility should be set as follows: 

 

1. 

Press the F key, this will cause the upper 

display to show set point 1 and the lower display 

will read SP1. 

 

2. 

Press the raise/lower keys to set desired 

temperature. 

 

3. 

Press the F key again and the upper display will 

show set point 2 and the lower display will read 

SP2, set the desired temperature for set point 2 

as above. 

 

4. 

Press the F key once more to return to the 

normal display. Under normal running 

conditions the upper display will show actual 

temperature and lower display will show desired 

temperature. 

 

5. 

To close/open the valve  manually press the 

HAND key, and the display will read actual 

temperature in the upper display and P in the 

lower display, the SET indicator will also flash. 

 

6. 

Press the raise key and the valve will move 

towards the open position. 

 

7.  

Press the lower key and the valve will move 

towards the closed position. 

 

8. 

Press the HAND key to return to normal display. 

All other parameters have been factory set, no 

attempt should be made to alter these without 

consulting Armstrong Holden Brooke Pullen. 

 

Dual Set Back Time Clock (if fitted) 

 

Set the time clock so that the ON periods represent set 

back times (set point 2). 

24 hour model: Turn dial so correct time coincides with 

the white triangle. 

7 day model: Turn dial so correct time and day coincides 

with the white triangle. 

Both models are complete with battery back up. 

The red and blue pins are inserted in the dial rim as 

required. A red pin marked 1 gives an ON operation, 

and a blue pin marked 0 gives an OFF operation. Both 

models have a manual override switch; 1  = ON, 0 = 

OFF. 

 

High Temperature Alarm 

 

Set the high temperature sensor (normally 12

?

C above 

set point) by adjusting the screw within the sensor body. 

NOTE: this sensor must be manually reset once tripped. 

(See G.A. for location). 

 

 

Operation Tests 

 

1. 

Switch on main power supply feeding unit. Turn 

isolator switch on control panel to the ON 

position, the mimic POWER ON indicator should 

now be illuminated. 

 

2. 

Turn pump selector switch to the ON position for 

one pump units or position 1 for two pump units. 

Check that PUMP 1 mimic indicator is 

illuminated. Repeat procedure for secondary 

pump if fitted. If a three phase supply is being 

used check pump  is running in the correct 

direction, if not reverse two phases at main 

isolator. On two pump units turn selector switch 

to PUMP 2 position and check PUMP 2 mimic 

indicator is illuminated. 

 

3. 

Press the  F key on the digital controller to enter 

HAND condition. Press the raise key and check 

valve is moving towards the open position, 

press the lower key and check valve is moving 

towards closed position. Press F key to return to 

normal display. 

 

4. 

On twin pump units turn pump selector switch to 

position 1. Trip circuit breaker 1 by pressing its 

red test button, this should stop PUMP 1 and 

start PUMP 2 automatically. Press green button 

to reset circuit breaker. 

 

5.  

Simulate a high temperature alarm by providing 

heat from the boiler and driving open the valve 

to admit heat, or adjust high temperature sensor 

to a lower setting. Once tripped the high 

temperature alarm indicator should be 

illuminated and the valve should motor to the 

closed position. The unit will remain shut down 

until the sensor is manually reset. 

ATTN

 

Reviews: