2.  Select a suitable location for system installation. Typically, the Astro 

system is mounted near the hot water heater. The inlet is connected to a 
return line from the furthest hot water tap in the system. The discharge is 
connected into the hot water heater drain line. 

3.  Ensure the following conditions are met when the system is mounted: 

i. 

The circulator shaft is horizontal. 

ii.  The clock/timer face is accessible for viewing and adjustment. 
iii.  The direction of water flow matches the arrow on the circulator casing. 
iv.  The piping is sufficiently rigid to support the system in operation. 
v.  Neither the clock/timer nor black terminal box is under the circulator. 

4.  The Astro system is shipped fully assembled and tested to suit either down 

discharge orientation with the clock timer facing up, or horizontal discharge 
with the clock timer facing the water supply side. For alternate orientation, see 

ROTATING THE CIRCULATOR CASING.

 

 

Top Timer  

Access, 

Down  

Discharge

 

 

Timer/Discharge 

Orientation 

(as shipped)

 

 

Side Timer  

Access, 

Horizontal 
Discharge

 

 

5.  Connect the hot water return line to the circulator, verifying proper flow direction. 

FLOW 

Fig. 1 Astro 2 Series circulator and 24-Hour Timer assembly drawing

Fig. 2 Astro 2 Series circulator and 24-Hour Timer wiring diagram 

TIMER

WHITE

WH

ITE

WHITE

GREEN

GREEN

BLACK

BLAC

K

BLAC

K

BLAC

K

BLACK

G

Green Ground

Screw in timer box


W

AQUASTAT

TIMER

WHITE

WHITE

WH

IT

E

WHITE

BLACK

BLACK

BLAC

K

BLAC

K

BLAC

K

BLACK

GREEN

G

Green Ground

Screw in timer box

Fig. 3 Astro 2 Series circulator and 24-Hour Timer and Aquastat Control wiring diagram 