It is important that the selected location for the equipment is suitable and 

can adequately accommodate the unit physical size, the unit weight and 

has safe and suitable access for correct operation and future maintenance 

requirements.

Location of Equipment

Minimum Access Requirements 

for Maintenance

• 

The unit must be mounted so that sufficient space is 

allowed for installation and service access.

• 

Maintenance personnel need to gain access to all 

parts of the unit and be able to remove components 

such as fans and filters via access doors as required.

• 

Unless otherwise specified the following minimum 

access should be available:

800mm clearance for electrical connections

1200mm for all access doors on the unit or if no 

access door is provided 1200mm from the front of 

the unit.

Noise Levels

• 

Do not locate equipment adjacent to sleeping 

quarters unless background noise levels have been 

checked and permitted by the appropriate authority.

• 

It is recommended that rubber supporting or 

vibration absorbing pads be used to support the unit 

to minimise any vibration being transmitted into the 

building structure. We recommend waffle pad to be 

used under the base frame and flexible couplings be 

fitted to the supply and return ducts to reduce any 

vibration transfer.

Fresh Air Inlet and Exhaust 

Air Outlet

• 

 The location of the fresh air inlets must adhere to the 

Australian Standards 1668.2.

• 

The fresh air intake should be positioned clear of 

any objects which could obstruct the airflow and be 

a minimum distance of 6 metres from any exhaust 

discharge ducts from this unit or any other adjacent 

equipment. Refer to Australian Standards AS 1668.2.

• 

The fresh air inlet and exhaust air outlet should 

be fitted with a cowl or other suitable means of 

weatherproofing.

• 

The exhaust discharge should be directed away from 

any openable windows.

Drainage

• 

Equipment should be installed with a positive fall 

to ensure water drains away freely through drain 

outlets. Drain lines must be as large as or larger than 

the fitting to which the line is being connected.

• 

All condensate drains must have a ‘P” Trap Fitted and 

have a minimum fall of 20mm per metre length.

• 

If drain lines are to be extended from the inside to the 

outside of the building they must be extended beyond 

walls of the building to eliminate the possibility of 

damage caused by drain water running down the 

exterior surface of the building wall.

• 

 When a drain is exposed to freezing temperatures or 

subject to the formation of condensation, the drain 

should be insulated.

IMPORTANT: ALL UNITS LOCATED IN PLANT ROOMS 

MUST HAVE DRAIN TRAYS UNDER THE COMPLETE UNIT.

  REM – Rotary Heat Wheel Unit Installation and Operation Manual 2021                    5

Summary of Contents for REM8000

Page 1: ...Installation and Operation Manual REM Rotary Heat Wheel Unit REM900 REM8000 M ADE A U STRALI A N Manufactured byArmcor M ADE A U STRALI A N Manufactured byArmcor...

Page 2: ...trical Requirements Mains Power Supply and Fusing Standard Equipment Layout 8 General Maintenance 9 General Monthly Maintenance Schedules Guide to How Frequency According to Usage is Established Three...

Page 3: ...om applications and includes energy saving EC Plug Fans in built bag filters and an option of enthalpy or sensible rotary heat wheels Every proposed installation must be subject to an engineered desig...

Page 4: ...recovery and or air handling equipment Installing and servicing equipment can be hazardous due to electrical and mechanical components When working on equipment observe precautions in all literature t...

Page 5: ...duce any vibration transfer Fresh Air Inlet and Exhaust Air Outlet The location of the fresh air inlets must adhere to the Australian Standards 1668 2 The fresh air intake should be positioned clear o...

Page 6: ...e to safety codes and guidelines Wear safety goggles work gloves work boots and protective clothing All external units are provided with substantial lifting lugs on each corner at the base frame NOTE...

Page 7: ...ommissioning Where a Heat Exchanger is incorporated in the equipment warranty is void if filters are not fitted IMPORTANT NEVER OPERATE A UNIT WITHOUT FILTERS FITTED TO THE RETURN FRESH AIR INTAKES El...

Page 8: ...Standard Equipment Layout Supply Air Exhaust Air Fresh Air Return Air 8 REM Rotary Heat Wheel Unit Installation and Operation Manual 2021...

Page 9: ...nsate drain if applicable for free drainage Guide to How Frequency According to Usage is Established Disposable Corrugated Filters Ordinary disposable corrugated filters should last approximately one...

Page 10: ...ices The original service call costs in identifying a warranty claim Freight and travel changes for work performed or parts supplied outside of all capital cities in Australia Field wiring refrigerant...

Page 11: ...voltage is available on all phases Check overload settings are correct if applicable Filters Check that both the fresh air and return air have adequate filters before starting unit Starting Unit Chec...

Page 12: ...xternal resistance Pa Measured downstream of fan outlets plus upstream of Coil s Estimate of Fresh Air Make Up or L s Electrical Supply Voltage Supply Fan Motor Amps Indoor Fan Motor Amps Boost Heater...

Page 13: ...Notes REM Rotary Heat Wheel Unit Installation and Operation Manual 2021 13...

Page 14: ...Notes 14 REM Rotary Heat Wheel Unit Installation and Operation Manual 2021...

Page 15: ...Notes REM Rotary Heat Wheel Unit Installation and Operation Manual 2021 15...

Page 16: ...au P 03 8301 9200 109 111 Northcorp Blvd Broadmeadows Vic 3047 2021 Armcor Air Solutions reserves the right to alter products and specifications without notice and does not accept responsibility for p...

Reviews: