Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
31
Basic configuration
The default password for basic configuration is 3333. After entering the
password, the first displayed menu will be Basic default configuration (indicating
the basic installer user level). For more information see “User level passwords
and indications” on page 27.
The basic configuration menu
Configuration options for this menu are shown in the table below. More
information for each option is included in the related topic.
Table 13: The basic configuration menu
Display
Menu
Values
Basic default configuration
01, 02, 05, 06, 11,12, 13, 14, 61, 63
EN 54-13 supervision
Of= EN54-13 supervision Off and
class B outputs
A= EN54-13 supervision On for
zone and class A expansion board
outputs
Default: Off
Panel mode
Basic standard
Basic evacuation
BS 7273 mode stage 1
BS 7273 mode stage 2
Repeater with fire routing (EN 54-2)
Repeater with fire routing (BS 7273)
Custom
Actuator delay
00 to 60 seconds
Default: 10 seconds
Reset disabled delay
00 to 30 minutes
Default: 2 minutes
Fire sounders delay
00 to 10 minutes
Default: 0 minutes
Fire routing delay
00 to 10 minutes
Default: 0 minutes
Add an expansion board [1]
00 to 04 modules
Default: 0
Firenet identifier [2]
0 to 32
0: Stand-alone (no networking)
Default: 0
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......