Heat pump water heater – OPERATING AND MAINTENANCE INSTRUCTIONS
54
F4
Empty tank (EMPTY), impressed
current anode circuit open
OFF
OFF
Verify whether there is any water in the tank, check or
replace the impressed current anode, if necessary.
F5
Short-circuit on the impressed
current anode circuit
ON
ON
Check or replace the impressed current anode if
necessary
8. MAINTENANCE (for authorized personnel)
WARNING! Observe the general warnings and safety instructions listed in the previous paragraphs
and strictly adhere to the indications therein contained.
All maintenance operations and interventions should be performed by qualified personnel (i.e. with the
necessary requirements as outlined in the applicable norms in force).
8.1 Draining the appliance
The appliance must be drained if left inactive in a room subject to frost.
When necessary, empty the appliance as follows:
-
Disconnect the appliance from the mains.
-
Close the shut-off valve, if installed, or the central tap of the domestic water supply network.
-
Open the hot water tap (washbasin or bathtub).
-
Open the cock on the safety device (in countries which acknowledge EN 1487) or the special cock installed on
the "T" fitting, as described in paragraph 4.10.
8.2 Routine maintenance
It is advisable to clean the evaporator on an annual basis in order to remove any dust or obstructions.
To access the evaporator, placed on the external unit, it is necessary to remove the fixing screws of the grid casing;
clean the evaporator with a flexible brush taking care not damage it. In the case you found some bended fins, straighten
them with a special comb, according to the fins spacing (1.6 mm).
Still on external unit, ensure that the condensate water runs out in a suitable drain and make sure the discharge is made
without hindrance.
Use only original spare parts.
After routine or extraordinary maintenance, we recommend filling the appliance's tank with water and draining it
completely to remove any residual impurities.
8.3 Troubleshooting
Problem
Possible reason
What to do
Water comes out
cold or
insufficiently
warm
Low temperature set
Increase the temperature set for the outlet water
Device functioning errors
Check for errors on the display and act in the way specified on the chart
"Faults"
No electrical connection, disconnected
or damaged wirings
Check the voltage at the supply terminals, verify the integrity and
connections of the cables.
Absence of HC/HP signal (if the product
is installed with the HC/HP signal cable)
Try to put the product in “Boost” mode, if is ok in this way, check the
connection of the meter, check the integrity of the HC/HP cable.
Malfunctioning of the timer for two-tier
rate (if the product is installed in this
configuration)
Check the operation of the contactor day / night and that the set time is
enough to heat water
Funcioning in “Voyage” mode
verify is not the programming period "Voyage", in that case deactivate the
function
Product off
Check availability of electricity, turn on the product
Usage of a large amount of hot water
when the product is heating up phase
Probe error
Control the presence, even if occasional E5
The water is
boiling (with the
possible
presence of
steam from the
taps)
High level of scaling of the boiler and
components
Turn off the power, drain the unit, remove the sheath of the resistance and
remove lime scale inside the boiler, be careful not to damage the enamel of
the boiler and the sheath resistance. Repackage the product as in the
original configuration, it is recommended to replace the flange gasket.
Probe error
Control the presence, even if occasional E5
Reduced
functioning
of
the heat pump,
semi-permanent
operation of the
Air temperature out of range
Depending from the climatic conditions
“Time W” value too low
Set a parameter for lower temperature or a longer unit of “Time W"
Installation done not in accordance with
electric voltage (too low)
Provide a proper Electric voltage
Evaporator clogged or frozen
Check the cleaning of the evaporator
Summary of Contents for Nuos Split Flex 200L
Page 2: ......
Page 145: ...3 1 2 ...
Page 146: ...4 ...
Page 147: ...5 6 7 8 11 9 10 Max pipe length 15m Max pipe length 15m ...
Page 148: ...12 270L 150L 200L 14 13 ...
Page 149: ...16 15 ...
Page 150: ......
Page 151: ......
Page 152: ...420010409904 ...