sistemas de protección de la caldera

boiler protection devices

43

The boiler is protected from malfunctions by means of internal 
checks performed by the electronic P.C.B., which stops the boiler 
from operating if necessary. In the event of the boiler being shut off  
in this manner, a code appears on the control panel display which 
refers to the type of shut-off  and the reason behind it.
Two types of shut-off  may occur:

Safety shut-off  

This type of error is “volatile”, which means that the boiler starts up 
again automatically as soon as the problem which caused the shut-
off  is removed.

The display will visualise the error code and description.

Fault 110

 - Send Probe Damaged”

In fact, soon as the cause of the shut-off  disappears, the boiler 
starts up again and continues to operate normally.
If the boiler still indicates a safety shut-off , switch it off . Make sure 
the external electric switch is in the OFF position, shut off  the gas 
valve and contact a qualifi ed technician.

Safety shut-off  due to insuffi

  cient water pressure

If the water pressure inside the heating circuit is insuffi

  cient, the 

boiler will perform a safety shut-off  .

The error code  “

Fault 108

 - Filling Needed”  appears on the display

The system may be restarted, re-balancing the value, by using the 
fi lling valve.

Check the pressure on the pressure gauge and close the valve as 
soon as it reaches 1 - 1.5 bar.

If the re-balancing request is performed on a frequent basis, switch 
the boiler off , bring the external electric switch to the OFF position, 
shut off  the gas valve and contact a qualifi ed technician to check 
for any leaks of water.

Operation shutdown

This type of error is “non-volatile”, which means that it is not 
removed automatically. 

The display will visualise the error code and description.

Fault 501

 - No fl ame detected - Press the Reset button”

In this case the boiler does not restart automatically, but it may be 
reset by pressing the  

 button. 

Fault 108

Filling Needed

ALERT

Fault 110

Send Probe Damaged

ALERT

Call the technical service

Fault 501

No flame detected

Press the Reset button

ALERT

Reset in progress

Fault solved

La caldera está protegida de los problemas de funcionamiento 
gracias a controles internos realizados por la placa electrónica que 
produce, si es necesario, un bloqueo de seguridad. 
En el caso de un bloqueo, se visualiza a través del led, el tipo de 
bloqueo y la causa que lo ha provocado.
Se pueden distinguir dos tipos:

Parada de seguridad

Este tipo de error, es del tipo “volátil”, o sea, se elimina 
automáticamente al cesar la causa que lo había provocado.
El display muestra el código y la descripción del error

Error 110

 - Sonda calef. defectuosa”

En efecto, apenas la causa del bloqueo desaparece, la caldera 
retoma su normal funcionamiento.
Si no es así, apague la caldera, lleve el interruptor eléctrico externo 
hasta la posición OFF, cierre el grifo de gas y llame a un técnico 
especializado.

Parada de seguridad por baja presión de agua

Si en el circuito de calefacción la presión del agua es insufi ciente, la 
caldera señala una parada de seguridad.
En el display aparecerá  Error 

108 - 

108 - 

Llenar la instalación

Llenar la instalación 

Es posible restablecer el funcionamiento del sistema reintegrando 
agua a través del grifo de llenado ubicado debajo de la caldera.
Controle la presión con el hidrómetro y cierre el grifo apenas se 
alcanzan los 1 - 1,5 bar. 
Si la demanda de reintegro fuera muy frecuente, apague la caldera, 
lleve el interruptor eléctrico externo hasta la posición OFF, cierre 
la llave de gas y llame a un técnico especializado para verifi car la 
presencia de posibles pérdidas de agua.

Parada por bloqueo

Este tipo de error es “no volátil”, esto signifi ca que no se elimina 
automáticamente.
El display muestra el código y la descripción del error
Para restablecer el normal funcionamiento de la caldera, presione 
el botón 

Reset

 en el panel de mandos.

El display muestra “Fase de reinicio” y luego “Error resuelto”

.

Si el problema vuelve a aparecer después de varios intentos de 
reset del aparato, contactar el servicio técnico.

Error 108

Llenar la instalación

ALERT

Abrir el grifo de llenado para retaurar la presión

ALERT

Error 110

Llenar la instalación

ALERT

Contacte con el centro de asistencia técnica

Error 501

Ausencia de llama

Pulsar la tecla Reset

ALERT

Fase de reinicio

Error resuelto

Summary of Contents for GENUS PREMIUM EVO HP

Page 1: ...MIUM EVO HP GENUS PREMIUM EVO HP 45 65 85 100 115 150 Installation and Servicing Instructions ES Instrucciones de instalaci n y de utilizaci n CALDERA MURAL A GAS A CONDENSACI N WALL HUNG CONDENSING G...

Page 2: ...de error 44 Funci n anticongelante 45 Area t cnica 46 Mantenimiento 59 Instrucciones para la apertura de la envoltura e inspecci n del interior 59 Mantenimiento 60 Informac n para el usuario 61 Simbo...

Page 3: ...ng directives 90 396 CEE relating to gas appliances 2004 108 CEE relating to electromagnetic compatibility 92 42 CEE relating to energy efficiency 2006 95 CEE relating to electrical safety Advertencia...

Page 4: ...das e inhalaci n o ingesti n de agentes qu micos nocivos Da o del aparato o de objetos cercanos debido a corrosi n con sustancias cidas Cierre herm ticamente los orificios utilizados para efectuar lec...

Page 5: ...mode selection summer winter 10 RESET button 11 Auto button To activate Thermoregulation 12 Heating temperature adjustument button Leyenda 1 Display 2 Botones regulaci n temperatura sanitario 3 Bot n...

Page 6: ...perature C only with external sensor connected Se alizaci n errores con indicaci n c digo y descripci n ALERT Error wsignals The display show the code and description Termorregulaci n activada auto AU...

Page 7: ...n del producto product description 7 Vista del Conjunto Overall wiew GENUS PREMIUM EVO HP 45 65 GENUS PREMIUM EVO HP 85 100 1 2 3 4 5 6 7 A C E 9 10 11 13 16 12 14 15 8 A C E 1 2 4 6 17 17 8 10 5 16 1...

Page 8: ...perature probe 15 C H Return temperature probe 16 Air relief valve 17 Connection for Safety valve A Central Heating Flow C Gas Inlet E Central Heating Return Leyenda 1 Tomas an lisis de humos 2 Termos...

Page 9: ...220 137 126 80 5 A C A C E F E F 465 888 97 81 81 162 140 232 25 586 54 74 75 123 A C E F A C E F A Central Heating Flow 1 M C Gas Inlet M E Central Heating Return 1 M F Condesate discharge A Central...

Page 10: ...140 231 26 586 115 696 150 A C E F A C E F GENUS PREMIUM EVO HP 115 150 A Central Heating Flow 1 1 2 M C Gas Inlet 1 M E Central Heating Return 1 1 2 M F Condesate discharge A Env o calefacci n 1 1 2...

Page 11: ...n la zona de humos del quemador en funciona miento 2 8 2 8 2 8 2 8 EMISIONES Presi n de aire disponible Pa 130 150 140 140 Clase NoX clase 5 5 5 5 Temperatura de humos G20 80 C 60 C max min C 68 63 68...

Page 12: ...24 0 25 0 25 Loss of burner gas when operating 2 8 2 8 2 8 2 8 EMISSIONS Available air pressure Pa 130 150 140 140 NOx class Less than 70 mg kWh class 5 5 5 5 Flue gas temperature G20 80 C 60 C C 67 6...

Page 13: ...24 0 24 P rdida en la zona de humos del quemador en funcionamiento 2 8 2 8 EMISIONES Presi n de aire disponible Pa 130 150 Clase NoX clase 5 5 Temperatura de humos G20 80 C 60 C max min C 68 63 68 63...

Page 14: ...ss when stopped T 50 C 0 15 0 15 Loss of burner gas when operating 3 2 3 1 EMISSIONS Available air pressure Pa 180 200 NOx class Less than 70 mg kWh class 5 5 Flue gas temperature G20 80 C 60 C C 76 6...

Page 15: ...os generadores instalados En especial el ambiente de instalaci n los dispositivos de seguridad y el sistema de evacuaci n de humos deben ser adecuados a la potencialidad total de la bater a de aparato...

Page 16: ...nstalaci n Coloque la caldera utilizando un nivel de burbuja 450 0 5 3 0 0 3 50 50 450 0 5 3 0 0 4 50 50 GENUS PREMIUM EVO HP 45 65 GENUSPREMIUMEVOHP85 100 115 50 Minimum clearances In order to allow...

Page 17: ...s para la conexi n hidr ulica y de gas de la caldera Vista de las conexiones Water connection The illustration shows the connections for the water and gas attachments of the boiler View of the Boiler...

Page 18: ...os de seguridad impuestos por la legislaci n GENUS PREMIUM EVO HP 85 100 115 150 no est previsto de una bomba Es necesaria la instalaci n de una bomba El circulador est disponible como un kit The hydr...

Page 19: ...er ir protegida por una v lvula termost tica o un bypass para impedir que se d una temperatura demasiado elevada en la zona del suelo Excessive pressure device The excessive pressure device outlet mus...

Page 20: ...rato se usa s lo para calefacci n el par metro de la caldera tiene que ser cambiado de Acumulador 1 a S lo calefacci n 2 en el par metro 2 2 8 Indirect cylinder connection The available kits allow for...

Page 21: ...utoridades locales y de los organismos encargados de la salud p blica Compruebe la colocaci n del tubo de evacuaci n de condensa ciones no lo doble al conectarlo evite que forme un cuello de cisne ase...

Page 22: ...uate the condensates When type B installation is used the room in which the coiler is installedmustbeventilatedusingasuitableairinletwhichcomplies with current legislation In rooms where corrosive vap...

Page 23: ...descarga m Maximum extension exhaust air m Di metro de los tubos mm Diameter of pipe mm 45 65 85 100 MIN MAX MIN MAX MIN MAX MIN MAX Sistemas coaxial Coaxial system C13 C33 C43 1 12 1 8 80 125 1 5 1...

Page 24: ...desde el exterior con terminal en el techo en el mismo campo de presi n Flue gas exhaust andair suction duct from outsidewithroof terminalin the same range of pressure C43 Descarga de humos y aspirac...

Page 25: ...please refer to the advice relating to the installation of these units H05V2V2 F 60 N L ATTENCION Antes de cualquier intervenci n en la caldera interrumpa la alimentaci n el ctrica utilizando el inte...

Page 26: ...K SOL TA1 CN1 OK Sensys 1 2 3 4 5 6 7 Control Remoto Remote Control Sonda externa External Sensor Termostato Ambiente Room Thermostat 1 Termostato acumulador Tank Thermostat BUS T B TA2 SE TNK SOL TA1...

Page 27: ...ng Fan V lvula desviadora motorizada option Diverter valve option Encendedor Ignitor V lvula de gas Gas valve Sonda env o calefacci n C H Flow temp probe Sonda retorno calefacci n Esquema el ctrico Pa...

Page 28: ...onexi n de Unidades Perif ricas Peripheral unit Conexiones Baja Tensi n LV connections Conexiones Alta Tensi n HV connections Conexiones Baja Tensi n LV connection Conexiones Alta Tensi n HV connectio...

Page 29: ...onnections Conexiones Baja Tensi n LV connection Conexiones Alta Tensi n HV connection Sensor de Ilama Detection electrode Ventilador modulante Modulating Fan V lvula desviadora motorizada option Dive...

Page 30: ...590280 Barra de instalaci n horizontal Frame horizontal support 3590283 Barra de instalaci n de suelo Frame foot 3590433 Kit de v lvula de cierre para caldera sola para modelos 45 65 kW Valve kit 45 6...

Page 31: ...35 85 100 115 150 Separador hidr ulico Hydraulic separator 3590436 45 65 Kit ACS para caldera sola System Kit for connecting the external indirect cylinder 3590437 85 100 Kit ACS para caldera sola Sys...

Page 32: ...instalaci n installation 32 GENUS PREMIUM HP EVO 45 65 145 39 42 75 75 765 186 95 186 122 745 19 186 91 189 66 122 126 199...

Page 33: ...EMIUM EVO HP 85 100 GENUS PREMIUM EVO HP 85 100 GENUS PREMIUM EVO HP 85 100 54 890 513 75 307 595 5 540 470 221 2x 121 2x 307 890 106 113 218 107 327 80 Rp2 Rp2 Rp2 Rp2 221 2x 122 2x 307 540 470 890 2...

Page 34: ...instalaci n installation 34 GENUS PREMIUM EVO HP 115 150 GENUS PREMIUM EVO HP 115 150 54 890 515 75 585 5 317 122 2x 221 2x 307 890 96 337 84 470 540 106 85 218 70 Rp2 Rp2 Rp2 Rp2...

Page 35: ...closed and then opened while the gas valve is disabled The meter must not show any signs of gas being used for 10 minutes Procedimiento de encendido Presione el bot n ON OFF el display se iluminar El...

Page 36: ...restored The cycle may either be repeated if necessary or stopped by pressing ESC Press the ESC button until the normal display screen is restored 01 01 2000 00 00 40 C 70 C Airpurge attiva Primer enc...

Page 37: ...g pressure Turn the encoder to select the maximum D H W power Wait for the boiler to stabilise before carrying out the combustion analyses Check the CO2 value according to the table below Important do...

Page 38: ...nci n limpieza activa girar el encoder para seleccionar Potencia m nima Importante no desmonte el silenciador si presente Nota Si la c mara de combusti n est abierta el valor de CO2 disminuye en un 0...

Page 39: ...s contenidas en la tabla de datos t cnicos Al finalizar la verificaci n desactive la Funci n Deshollinador y vuelva a colocar correctamente la tapa y la junta Wait a few seconds until the CO2 stabilis...

Page 40: ...su apagado para acercarse a la temperatura de mantenimiento Si se selecciona manual se puede ajustar el anticiclo en el par metro 2 3 6 de 0 a 7 minutos Si se selecciona autom tico la caldera calcula...

Page 41: ...8 NO 6 8 NO 6 0 NO 6 2 Caudal de gas m x m n Gas flow max min 15 C 1013 mbar Nat m3 h LPG kg h max 3 8 3 2 5 3 4 5 7 3 6 3 8 1 6 9 min 1 1 1 0 1 6 1 4 1 8 1 6 2 0 1 7 Par metro Parameter 115 150 G20...

Page 42: ...uencia del detector ambiente permite regular la influencia del detector ambiente sobre el c lculo de la temperatura de set point de impulsi n 20 m xima 0 m nima AUTO function This is a function which...

Page 43: ...the Reset button ALERT Reset in progress Fault solved La caldera est protegida de los problemas de funcionamiento gracias a controles internos realizados por la placa electr nica que produce si es nec...

Page 44: ...mostat contact open 118 Heating delevery probe problem 1P1 Insufficient circulation indication 1P2 1P3 1P4 Insufficient water request filling D H W circuit 203 Tank Probe Damaged 205 DHW In Probe Open...

Page 45: ...The anti frost device activates only when with the boiler operating correctly the system pressure is correct the boiler is electrically powered there is a supply of gas External P C B s 411 Zone 1 Ro...

Page 46: ...programming key Insert technical code 222 Insert code Save Complete Menu Configuration Wizard Service Faults Technical area Language date and time REA T CNICA reservada para el t cnico cualificado El...

Page 47: ...miento Errores Men rea t cnica Idioma fecha y hora 1 No disponible 2 Parametros Caldera 3 No disponible 4 Par metros Zona 1 Men 0 Red Example Modification of parameter 2 3 1 Max Adjustable Central Hea...

Page 48: ...830 Proceso guiado Llenado instalaci n Desaeraci n instalaci n Analisis humos Opciones de asistencia Datos centro de asistencia Para insertar nombre y tel fono del Centro de Asistencia Los datos apar...

Page 49: ...s Direct access to the parameters 402 502 602 420 520 620 434 534 634 830 Guided procedures System Filling System air purge Exhaust fumes analysis Service options Service Center Data To insert the nam...

Page 50: ...100 60 see Table summarising changes men submen par metro Descripci n Campo de regulaci n Confi guraciones de f brica C DIGO DE ACCESO 222 gire el encoder en sentido horario para seleccionar el c dig...

Page 51: ...rning 1P4 Filling Needed ALERT 2 4 3 Post ventilation after Central Heating request 0 OFF 1 ON 0 men submen par metro Descripci n Campo de regulaci n Confi guraciones de f brica 2 3 2 Porcentaje Pot n...

Page 52: ...3 minutes post circulation and post ventilation after domestic hot water draw off 2 5 5 Delay start in Central Heating after D H W request from 0 to 30 minutes 0 2 4 4 Tiempo Incremento temp Calefacc...

Page 53: ...ampo de regulaci n Confi guraciones de f brica menu sub menu parameter description value default setings 2 5 7 Funci n antilegionela 0 OFF 1 ON 0 Activado con caldera conectado con acumulador esterno...

Page 54: ...menu sub menu parameter description value default setings 4 2 2 Curva Termorregulaci n Zona1 de 0 2 a 0 8 baja temperatura 0 6 de 1 0 a 3 5 alta temperatura 1 5 Cuando se utiliza la sonda externa la c...

Page 55: ...rease decrease In the flow temperature with respect to the set point value men submen par metro Descripci n Campo de regulaci n Confi guraciones de f brica menu sub menu parameter description value de...

Page 56: ...aci n Confi guraciones de f brica menu sub menu parameter description value default setings 5 2 4 Zona2 Influencia Ambiente de 0 a 20 20 Seleccionar la influencia del detector ambiente para el c lculo...

Page 57: ...e regulaci n Confi guraciones de f brica menu sub menu parameter description value default setings 6 2 3 Zona 3 Desplazamiento de 7 a 7 baja temperatura 0 de 14 a 14 alta temperatura 0 Para adaptar la...

Page 58: ...List Reset Ok Yes Esc No men submen par metro Descripci n Campo de regulaci n Confi guraciones de f brica menu sub menu parameter description value default setings 8 4 SOLAR HERVIDOR 8 4 0 Temperatur...

Page 59: ...dos clip del panel de cierre de la c mara de combusti n Tirarlo hacia delante y desengancharlo de los pernos superiores c Instructions for opening the casing and performing an internal inspection 45 6...

Page 60: ...vaciados si se usa dicho l quido verifique atentamente su compatibilidad con el acero inoxidable que constituye el cuerpo de la caldera Maintenance is an essential part of the safe and efficient opera...

Page 61: ...ratura y configurar los dispositivos de regulaci n para lograr una administraci n de la instalaci n correcta y m s econ mica Exigir el mantenimiento peri dico de la instalaci n seg n lo indicado por l...

Page 62: ...ma de funcionamiento 21 Temperatura m xima de calefacci n 22 Temperatura m xima del circuito sanitario Gas MAX MIN Gas mbar mbar 1 2 5 4 3 6 7 19 8 9 10 11 12 14 15 16 17 18 13 20 21 22 Symbols used o...

Page 63: ......

Page 64: ...Nord Plaza Xavier Cugat n 2 Edificio A 2 08174 Sant Cugat del Vall s Barcelona www ariston com info es ariston com TEL FONO ATENCI N CLIENTE 902 89 81 81 Ariston Thermo SpA Viale A Merloni 45 60044 F...

Reviews: