WARNING 
Before performing any work on the boiler, fi rst 
disconnect it from the electrical power supply using the 
external bipolar switch.

Electrical connections

For increased safety, ask a qualifi ed technician to perform a 
thorough check of the electrical system. 
The manufacturer is not responsible for any damage caused by the 
lack of a suitable earthing system or by the malfunctioning of the 
electricity mains supply. 
Make sure that the system is able to withstand the maximum 
power absorbed by the boiler (this is indicated on the appliance 
data plate). Check that the section of the wires is suitable and is not 
less 1,5 mm

2

 

The appliance must be connected to an effi

  ecient earthing system 

if it is to operate correctly.
The power supply cable must be connected to a 230V-50Hz 
network, where the L-N poles and the earth connection are all 
respected.
 Important!
In the event that the power supply cable must be changed, replace 
it with specifi que cable supply by ARISTON.

Important!
Connection to the electricity mains supply must be 
performed using a fi xed connection (not with a mobile 
plug) and a bipolar switch with a minimum contact 
opening of 3 mm must be fi tted.

The use of multiplugs, extension leads or adaptors is strictly 
prohibited. 
It is strictly forbidden to use the piping from the hydraulic, heating 
and gas systems for the appliance earthing connection. 
The boiler is not protected against the eff ects caused by lightning. If the 
mains fuses need to be replaced, use 2A rapid fuses.

WARNING 
For the connection and positioning of the wires belonging to 
optional peripheral units, please refer to the advice relating to 
the installation of these units.

H05V2V2-F

60

N

L

Peripheral unit connection

To access peripheral unit connections carry out the following steps:
 -   Disconnect the boiler from the power supply
 -   Remove the casing by unhooking it from the instrument panel
 -   Rotate the control panel while pulling it forwards
 -   Unhook the two clips “a”, rotate the cover “b” to have access to 

the peripherical connections

 -   Unscrew the two screws “c” and remove the cover “d” of the 

instrument panel to have access to the main P.C.B.

Peripheral connections:

BUS = 

Remote control connection (modulating device)

FLOOR/ TA2 = 

the underfl oor heating thermostat or the room 

thermostat 2 

(selected via parameter 223 - factory setting = 

underfl oor heating thermostat)

SE =  

Outdoor sensor - OPTION

TNK

 =  Tank temperature probe 

SOL =   

Solar temperature probe

TA1 =   

Room thermostat 1

a

b

c

d

BUS

T

B

FLOOR

TA2

SE

TNK

SOL TA1

CN1

OK

Sensys 

1

2

3

4

5

6

7

Remote Control

External Sensor

Room Thermostat 1

Tank Sensor

Summary of Contents for GENUS PREMIUM EVO HP 100

Page 1: ...GENUS PREMIUM EVO HP WALL HUNG CONDENSING GAS BOILER GENUS PREMIUM EVO HP 45 65 85 100 115 150 Installation and Servicing Instructions...

Page 2: ...e gas exhaust duct lengths 18 Type of air suction flue gas exhaust ducting 18 Electrical connection 19 Peripheral unit connection 19 Electrical diagram 45 65 20 Electrical diagram 85 100 21 Electrical...

Page 3: ...s not the case please contact your supplier Keep all packaging material clips plastic bags polystyrene foam etc out of reach of children as it may present a potential hazard In the event of a fault an...

Page 4: ...the ladder and parapets on the landing Personal injury caused by falling from a height During all work carried out at a certain height generally with a difference in height of more than two metres mak...

Page 5: ...t temperature XX C D H W operation set D H W set temperature active with indirect cylinder connected XX C D H W operation active D H W set temperature active with indirect cylinder connected XX C Exte...

Page 6: ...product description 6 Overall wiew GENUS PREMIUM EVO HP 85 100 GENUS PREMIUM EVO HP 45 65 1 2 3 4 5 6 7 A C E 9 10 11 13 16 12 14 15 8 A C E 1 2 4 6 17 17 8 10 5 16 12 7 14 15...

Page 7: ...glass 4 Ignition electrode 5 Ignitor 6 Modulating fan 7 Minimum water pressure switch 8 Siphon 9 Circulation pump with air release valve 10 Mixer 11 Silencer 12 Gas valve 13 Detection electrode 14 C...

Page 8: ...81 81 162 140 232 25 586 54 74 75 123 A C E F A C E F Overall Dimensions A Central Heating Flow 1 M C Gas Inlet M E Central Heating Return 1 M F Condesate discharge A Central Heating Flow 1 M C Gas In...

Page 9: ...uct description 9 A Central Heating Flow 1 1 2 M C Gas Inlet 1 M E Central Heating Return 1 1 2 M 465 888 81 81 162 97 54 74 123 75 140 231 26 586 115 696 150 A C E F A C E F GENUS PREMIUM EVO HP 115...

Page 10: ...24 0 25 0 25 Loss of burner gas when operating 2 8 2 8 2 8 2 8 EMISSIONS Available air pressure Pa 130 150 140 140 NOx class Less than 70 mg kWh class 5 5 5 5 Flue gas temperature G20 80 C 60 C C 67 6...

Page 11: ...band Loss when stopped T 50 C 0 15 0 15 Loss of burner gas when operating 3 2 3 1 EMISSIONS Available air pressure Pa 180 200 NOx class Less than 70 mg kWh class 5 5 Flue gas temperature G20 80 C 60 C...

Page 12: ...m other appliances unless the flue is meant to serve more than one user in accordance with current legal requirements Where there is already a connection to existing flue exhausts check that these exh...

Page 13: ...he supplied gas corresponds to the type of gas for which the boiler was designed see the data plate located on the appliance itself It is also important to check that the pressure of the gas methane o...

Page 14: ...ure device outlet must be connected to a drainage siphon which can be checked visually in order to prevent maintenance procedures causing harm to people animals or property the manufacturer shall not...

Page 15: ...n the system is frequently refilled with water In such cases if the system is then partially or totally drained it must be refilled using treated water again Discharge of condensation High energy effi...

Page 16: ...air vent 2 Main heat exchanger 3 Detection Electrode 4 C H Flow temperature probe 5 C H Return temperature probe 6 Minimum water pressure switch 7 Siphon 8 Circulation Pump optional for 85 100 115 150...

Page 17: ...ation is used the room in which the coiler is installedmustbeventilatedusingasuitableairinletwhichcomplies with current legislation In rooms where corrosive vapours may be present for example laundry...

Page 18: ...xternal wall Type Maximum extension exhaust air m Diameter of pipe mm 45 65 MIN MAX MIN MAX Coaxial system C13 C33 C43 1 12 1 8 80 125 B33 1 12 1 8 80 125 Twin pipe System C13 C23 C33 C43 S1 S2 S1 S2...

Page 19: ...multiplugs extension leads or adaptors is strictly prohibited It is strictly forbidden to use the piping from the hydraulic heating and gas systems for the appliance earthing connection The boiler is...

Page 20: ...upply N N FLAME L L BUS T B TA2 SE TNK SOL TA1 CN14 CN13 CN9 1 CN19 CN1 1 1 CN8 1 CN6 1 1 Peripheral unit LV connections HV connections HV connection N N FLAME L L CN19 CN2 CN11 1 1 Gr Detection elect...

Page 21: ...N18 1 1 Gr Detection electrode Fan Rd Wh LV connection Display C H Return temp probe C H Flow temp probe Minimum water pressure switch Rd Rd Bl Bl Bl Bk CN14 CN3 1 1 CN8 1 CN25 1 Ignitor Diverter valv...

Page 22: ...N19 CN2 CN11 1 1 Gr Detection electrode Fan CN11 1 LV connection Display C H Return temp probe C H Flow temp probe Minimum water pressure switch Rd Rd Bl Bl Bl Bk CN14 CN3 1 1 CN8 1 CN25 1 Ignitor Div...

Page 23: ...ures To guarantee safety and the correct operation of the appliance the boiler must be prepared for operation by a qualified technician who possesses the skills which are required by law Electricity s...

Page 24: ...iler 6 The exhaust duct for combustion products should be suitable and free from any obstructions 7 Any necessary ventilation inlets in the room should be open type B installation 8 Check whether the...

Page 25: ...ming out of the boiler may be more than 65 C The display will visualise the Chimney Function active at the maximum heating pressure Turn the encoder to select the maximum D H W power Wait for the boil...

Page 26: ...ion procedure is completed check the CO2 values once again at maximum power If the recorded values fall within the limits indicated in the tables no further calibration is necessary After these operat...

Page 27: ...gas cock 3 disconnect the electrical connections to the boiler 4 gain access to the combustion chamber as indicated in the paragraph Maintenance Guide General Access 5 add remove the gas diaphragm as...

Page 28: ...llowing parameters must be set 4 2 1 Activation of temperature adjustment using sensors Select 01 outdoor sensor only 4 2 2 Temperature adjustment curve selection Select the relevant curve according t...

Page 29: ...omatically but it may be reset by pressing the button Fault 108 Filling Needed ALERT Fault 110 Send Probe Damaged ALERT Call the technical service Fault 501 No flame detected Press the Reset button AL...

Page 30: ...vation of the anti frost safety device is signalled on the display by the symbol The anti frost device activates only when with the boiler operating correctly the system pressure is correct the boiler...

Page 31: ...of parameter 2 3 1 Max Adjustable Central Heating Power Proceed as follows 1 Simultaneously press the ESC and buttons for 5 seconds the display will visualise the request for entering the technical co...

Page 32: ...ct access to the parameters 402 502 602 420 520 620 434 534 634 830 Guided procedures System Filling System air purge Exhaust fumes analysis Service options Service Center Data To insert the name and...

Page 33: ...ge from 0 to 100 100 RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is changed see Table summarising changes 2 3 3 Minimum power percentage from 0 to 100 100 RESERVED FOR TECHNICAL ASSISTANC...

Page 34: ...irculation and post ventilation after domestic hot water draw off 2 5 5 Delay start in Central Heating after D H W request from 0 to 30 minutes 0 2 5 7 Anti legionella Function 0 OFF 1 ON 0 Activated...

Page 35: ...alculate the set point temperature Thermoregulation enabled from 0 to 20 20 If setted 0 the room temperature doesn t influence the calculation of the set point If setted 20 the room temperature has th...

Page 36: ...0 8 low temperature 0 6 See parameter 422 Only enabled when an outdoor sensor is installed When an outdoor sensor is used the boiler calculates the most suitable delivery temperature taking into accou...

Page 37: ...to next maintenance from 0 to 60 month 24 If setted the boiler will display that is time to call the installer for maintenance Warning 3P9 Sched Maintanace Call Service ALERT 8 5 1 Enable Maintenance...

Page 38: ...it forwards d 4 Unhook the two clips on the panel closing off the combustion chamber Pull it forwards and unhook it from the upper pins e Instructions for opening the casing and performing an internal...

Page 39: ...dded to the water in the heating system in order to avoid the need for repeated draining when this liquid is used make sure it is compatible with the stainless steel used for the bodywork of the boile...

Page 40: ...try gas category 7 Gas setting 8 Installation type 9 Electrical data 10 Maximum domestic hot water pressure 11 Maximum heating pressure 12 Boiler type 13 NOx class Efficiency 14 Input rating nominal h...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...420010271304 Asistencia T cnica 902 196 547 Ariston Thermo SpA Viale A Merloni 45 60044 Fabriano AN www aristonthermo it info it aristonthermo com...

Reviews: