Parameter Function
Adjustment range
Factory settings
1
Ignition power as %
00
to
99 %
(step: 1%)
55
Consult the manufacturer
before changing this
parameter
2
Maximum heating power (%)
00
to
99 %
(step: 1%)
66
3
Anti-cycle timer (minutes)
00
to
07 minutes
(step: 1 minute)
02
4
Minimum heating outlet temperature
25° to 42 °C if parameter
r
= 00
42° to 81 °C if parameter
r
= 01
42
5
Maximum heating outlet temperature
26° to 75 °C if parameter
r
= 00
43° to 82 °C if parameter
r
= 01
82
6
Not used
00
to
99
45
tS
E@sy remote surveillance
0
or
1
0
Do not alter if the E@sy
system is not connected
F
Type of boiler
00
to
03
03
do not alter (boiler
with tank)
E
External actuator (depending on system)
00
to
03
00
do not alter
P
Post-circulation with pump in heating mode
from
01
to
15
minutes or
C0
02
C
Activation/deactivation of Domestic hot
water function
00
or
01
00
PU
Pump speed control
U0
or
U1
U1
r
Heating setpoint range
00
or
01
01
P
Temperature control by external sensor
90
or
91
90
P6
Gradient shift
-
20
to +
20 °C
0
P5
Gradient adjustment
0_1
to
5_0
0_9
T
Test function
Not used
A
Not used
b0
Second zone set-point
25
to
82
75
b1
Not used
b2
Post Domestic hot water timer in minutes
00
to
30
00
b3
Not used
b4
Programmer action
0
to
2
0
on heating and tank reheating
1
on tank reheating
2
on heating
0
b5
Not used
b7
Not used
b8
Not used
Important!! The parameters
P5
,
P6
and
P9
are only activated if the external sensor is connected.
To return to the standard displays, press the Menu button.