GB - 11
- Set the dip switch on the sensor’s pcb to
ON (fi g. 3).
- Hold the button on the receiver down for 5
seconds (fi g. 4); the red led will start fl ashing.
The receiver is now ready to receive the
signal.
- Press the button on the outdoor sensor’s
pcb until the red led A turns on for 2 sec-
onds (fi g. 5). Now press the button again to
send the temperature measurement to the
receiver.
- Wait a few seconds for the association pro-
cedure to terminate.
If the procedure has terminated success-
fully, the red led on the receiver will go out.
The receiver and sensor are now ready for
normal operation.
If the association procedure fails, the red led
on the receiver will stay on. In this case, re-
peat the procedure as described above.
More than one receiver can be associated
with a single outdoors wireless sensor. Re-
peat the procedure as described above for
each receiver.
Deleting the association
Hold the button on the receiver down for 15
seconds, the red led will fl ash quickly 5 times.
Once the association has been deleted, the
receiver’s red led will stay on.
installation
ON
fi g. 3
ON
ON
O
O
O
O
fi g. 4
fi g. 5
A
LED
STATUS
DIAGNOSIS
GREEN
OFF
controller not powered on
ON
controller powered on
RED
OFF
receiver associated
slow fl ashing
association procedure running
rapid fl ashing
radio communications error
ON
receiver not associated
Troubleshooting
ERROR
CAUSE
SOLUTION
114
External sensor fault
- receiver incorrectly hooked up electrically
- battery dead
- no association between the devices
- sensor and receiver out of range of each other
- check the electrical hookup
- replace the sensor
- repeat the association procedure
- use a radio signal repeater
Warning:
error 114 displays only if the outdoors sensor thermoregulation function is active. If the thermoregulation
function is not active, the display will not show the outdoors temperature.