7.5.12 FMAX System Flow Rate
Range - 0 to 6.0 l/min ~ Default 6.0 l/min
FMAX is only displayed when OHQM is set to On.
Enter the actual flow rate as set on the pump module - see fig 7.5B, also
refer to Pump Manual.
F
IG
. 7.5
B
F
LOW
R
ATE
S
ETTING
FMAX
6.0l /min
MEDT
1
MED%
45%
HND1
Auto
Only when OHQM is On
Only when OHQM is On
Only when OHQM is On
Only when MEDT is 1 or 2
7.5.13 MEDT Antifreeze type
Range - 0 to 3 ~ Default 1
MEDT is only displayed when OHQM is set to On.
Set 0
for
Water
Set 1
for
Propylene glycol
Set 2
for
Ethylene glycol
Set 3
for
Tyfocor (supplied with SOLARcomfort)
7.5.14 MED% Concentration of Antifreeze
Range - 20% to 70% ~ Default 45%
MED% is only displayed when OHQM is set to On and MEDT is set to
1 (Propylene glycol) or 2 (Ethylene).
Set value to the dilution of the antifreeze used in the system.
As Tyfocor is supplied with the system MED% will not be required.
7.5.15 HND1 Operating Mode of R1
Range - Off, Auto, On ~ Default Auto
Auto must be selected for normal operation.
On and Off should only used during commissioning and setting up.
On
Relay R1 On, solar pump running.
Indicator light flashes red/green
and
flashes on display.
Off
Relay R1 Off, solar pump off.
flashes on display -
does not flash.
7.5.16 HND2 Operating Mode of R2
Range - Off, Auto, On ~ Default Auto
HND2 is only used when Arr 2 is set.
Auto must be selected for normal operation.
On and Off should only used during commissioning and setting up.