user’s manual

Operation shutdown error table

Anti-frost Device. 

The anti-frost function acts on the central heating fl ow temperature 
probe, independently from other settings, when the electrical 
supply is turned on.
If the primary circuit temperature falls below 8°C the pump will run 
for 2 minutes.
After the two minutes of circulation (fi xed) the boiler will check the 
following:
a)  if the central heating fl ow temperature is > 8°C, the pump stops;
b)  if the central heating fl ow temperature is between 4 and 8°C, 

the pump will run for another two minutes;

c)  if the central heating fl ow temperature is < 4°C, the burner will 

fi re (heating position) at minimum power until the temperature 
reaches 33°C, the burner will go off  and the pump will continue 
to run for two minutes.

The anti-frost device activates only when (with the boiler operating 
correctly):
-  the system pressure is correct,
-  the boiler is electrically powered,
-  there is a supply of gas.

Change of gas type 

 

Our boilers are designed to function either with Natural Gas 
(methane) or L.P.G. gas. If you need to change from one gas to the 
other, one of our Authorised Service Centres must be contacted to 
convert the appliance.

Maintenance

 Schedule an annual maintenance check-up for the boiler with a 
competent person.
Correct maintenance always results in savings in the cost of 
running the system.
Failure to arrange an annual service for the appliance will invalidate 
the second year and subsequent years of the manufacturers 
guarantee. 

Appliance shut-off  conditions

The boiler is protected from malfunctions by means of internal 
checks performed by the electronic P.C.B., which stops the boiler 
from operating if necessary. In the event of the boiler being shut off  
in this manner, a code appears on the control panel display which 
refers to the type of shut-off  and the reason behind it.
Two types of shut-off  may occur:

Safety shut-off 

This type of error is “volatile”, which 
means that the boiler starts up 
again automatically as soon as the 
problem which caused the shut-off  
is removed. 
The display will fl ash ”Err” and the 
error code.
In fact, as soon as the cause of the 
shut-off  disappears, the boiler starts 
up again and continues to operate normally. 
While the boiler is shut off  for safety reasons, it is possible to 
attempt to restore normal operation by switching the appliance off  
and on again using the ON/OFF button on the control panel.
If the boiler still indicates a safety shut-off , switch it off . Make sure 
the external electric switch is in the OFF position, close the gas tap 
and contact a qualifi ed technician.

Safety shut-off  due to insuffi

  cient water pressure

If the water pressure inside the 
heating circuit is insuffi

  cient,  the 

boiler will perform a safety shut-off . 
(See table).
To re-pressurise the boiler, it will 
be necessary to connect the silver 
fl exible hose supplied to the two 
isolating points underneath the 
boiler, once the hose is connected, 
open up both of the black quarter 
(see p.5)  turn handles, once the pressure reads 1.5 bar on the 
display, close both handles and disconnect the hose .
If the pressure drops very frequently, there may be a water leak 
at some point in the system. If this is the case please contact your 
installer and ask them to check it.

Operation shutdown

This type of error is “non volatile”, which means that it is not 
removed automatically. The display will fl ash 

Err

 and the error 

code.
In this case the boiler does not restart automatically, but it may 
be reset by pressing the  

 button. If the problem manifests 

itself again after several attempts to reset the appliance, contact a 
qualifi ed technician.

IMPORTANT
IF THIS SHUTDOWN OCCURS FREQUENTLY, CONTACT AN 
AUTHORISED SERVICE CENTRE FOR ASSISTANCE. FOR SAFETY 
REASONS, THE BOILER WILL ALLOW A MAXIMUM OF 5 RESET 
OPERATIONS TO TAKE PLACE IN 15 MINUTES (INDIVIDUAL 
PRESSES OF THE 

 BUTTON).

Display

Description

 

1 01

Overheating

5 01

No fl ame detection

1 03

Insuffi

  cient circulation

1 04

1 05

1 06

1 07

1 08

Insuffi

  cient water (request fi lling)

3 05

P.C.B error

3 06

P.C.B error

3 07

P.C.B error

Summary of Contents for 41-116-36

Page 1: ... HE EVO CLAS HE EVO System CONDENSING WALL HUNG GAS BOILER G C N 47 116 65 24 kW G C N 47 116 66 30 kW G C N 47 116 67 38 kW G C N 41 116 36 18 kW G C N 41 116 37 24 kW G C N 41 116 38 30 kW Country of Destination GB IE ...

Page 2: ... either by material or workmanship of the manufacturer This guarantee does not protect malfunction or damage arising from incorrect installation commissioning or maintenance procedures as laid out in the installation and servicing manual inefficient flue system poor or incorrect electricicty wrong gas supply or pressure tampering by inexperienced persons and any other cause not directly due to man...

Page 3: ...CEE relating to gas appliances 2004 108 CEE relating to electromagnetic compatibility 92 42 CEE relating to energy efficiency 2006 95 CEE relating to electrical safety Safety regulations Key to symbols Failure to comply with this warning implies the risk of personal injury in some circumstances even fatal Failure to comply with this warning implies the risk of damage in some circumstances even ser...

Page 4: ...tton 10 TIME CLOCK option for System boilers 11 RESET button 12 Heating temperature adjustument button Digits indicating boiler status and temperature indication C error code signals Err menu settings Technical assistance request Flame detected with indication of power used or indication of operation shutdown Heating operation set Heating operation active Hot water operation set Hot water operatio...

Page 5: ...ing CLAS HE EVO System The figures indicates the flow temperature when no heating requests have been made the flow temperature in central heating mode the temperature of the hot water in domestic hot water Operating mode selection Use the MODE button 3 to select the desired operating mode Operating mode Display heating hot water production for domestic use winter hot water production for domestic ...

Page 6: ...witching off the boiler To switch off the boiler press the ON OFF button the display will switch off The Anti frost Function is already active ATTENTION Switch off the boiler completely by switching the external electri cal switch to the OFF position Shut off the gas valve Adjusting the heating It is possible to set the temperature of the heating water by pressing the buttons 12 The temperature th...

Page 7: ...you on the devices connectable to the boiler and will program it according to the system In normal boilers the water temperature inside the heating elements is usually set to a high value 70 80 C thereby ensuring effective heating during the few really cold winter days It then becomes excessive on less cold days of which there are many more typical of the autumn and winter seasons This leads to ex...

Page 8: ...which means that the boiler starts up again automatically as soon as the problem which caused the shut off is removed The display will flash Err and the error code In fact as soon as the cause of the shut off disappears the boiler starts up again and continues to operate normally While the boiler is shut off for safety reasons it is possible to attempt to restore normal operation by switching the ...

Page 9: ......

Page 10: ......

Page 11: ... to attend to the appliance and the failure is caused by either an installation error user error or any other external cause then a waste call charge will be made If the waste call charge is not paid then any extended warranty will cease The 5 Year Guarantee is only applicable to appliances installed in the United Kingdom The following is not covered under the guarantee Any external boiler control...

Page 12: ...ston Thermo UK Ltd Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone 01494 755600 Fax 01494 459775 Internet www ariston co uk Technical Advice 0333 240 7777 Customer Service 0444 240 8777 420010439300 ...

Reviews: