9.0
Remote status / control
Please see individual terminal software information and Figure #17 for a remote terminal screen
format.
9.1
Remote Terminal Status Format
The following is a typical screen page layout as the RSM responds to the “status” command after
selecting a module (please note that the screen shown may vary for different models).
010-030-C0 Rev E Page 42 of 42
ARGUS TECHNOLOGIES
*****************************************
RSM Module Status VX.XX
************************************
Module ID #: xx
Serial No: xxxxxxxxxxxxxxxx
Model: xxxxxxxxxxxxxxxx
**********************************************************************************************************************
Operational Status
—————————
Float/Equalize Mode
Input Volts = xxxVAC
Current Limit/blank
Output Current = xx.xADC
Output Voltage = xx.xVDC
Fan Speed/Set = spd/spd
Int Amb Temp = xxxC
Auto/Manual test/blank
Remote Equalize
Remote Shutdown
Start Delay = xxx Sec/SS
Heat Sink Temp = xxxC
Module Settings
————————
Float = xx.xVDC
Equalize = xx.xVDC
Load Share = Forc/Slope
OVP Shutdown = xx.xVDC
Low O/P Alarm = xx.xVDC
Slope = x.xx%
O/P I Limit = xx.xA
Equalize Timeout = xxhrs
Start Delay = xxx Sec
Backlight Tmout = xxMin
I limit Alrm = En/Dsabled
Local Access Alrm E/Dable
High O/P Alarm = xx.xV
Module Alarms
———————
REMOTE SHUT DOWN
REMOTE EQUALIZE
O/P BREAKER OPEN
I/P BREAKER OPEN
AC MAINS FAIL
AC MAINS HIGH
FAN FAIL
MODULE FAIL
OVER TEMPERATURE
O/P HV SHUTDOWN
LOW O/P VOLTAGE
CURRENT LIMIT
TEMP SENSE FAIL
FAN SPEED ERROR
UPF HIGH TEMPERATURE
Figure 17 - Remote Screen Layout