4.4.3
Battery Connection
Remove the battery fuse(s) before connecting or disconnecting the battery cables from the battery
and/or charger.
1/4” - 20 studs for up to #8 AWG wire. Charger supplies current to the battery through these con-
nections. Current also flows from the battery into these connections to the Load Connection when
the battery is connected to the load.
4.4.4
Load Connection
Remove the battery fuse(s) before connecting or disconnecting the load cables from the load and/or
charger.
1/4” - 20 studs for up to #8 AWG wire. Battery current flows from these terminals to the load during
a transfer condition. The transfer circuit senses the voltage at these terminals to determine when to
connect the battery to the load.