User
Manual
39
Fig. 5.3 Unit On/Off time setting in unit On status
Page 1: ...Wifi optional Thank you for choosing this product Read this Manual carefully before using the appliance and keep it for future reference In case of loss of this User Manual visit the www argoclima com...
Page 2: ...sion or instruction concerning use of the appliance by a person responsibility for their safety Children should be supervised to ensure that they do not play with the appliance 2 This instruction manu...
Page 3: ...isposed of as an household waste It must be taken to special local community waste collection centres or to a dealer providing this service Disposing of electrical and electronic equipment separately...
Page 4: ...4 3 2 LCD Display Instruction 4 4 Installation and Commissioning 7 4 1 Instruction of wired controller 8 4 2 Commissioning 16 5 Operation Instructions 33 5 1 ON OFF 33 5 2 Mode Setting 33 5 3 Tempera...
Page 5: ...sence Setting 48 5 16 Remote Shield Function 49 5 17 Child Lock Function 49 5 18 Gate Control Function 49 5 19 Inquiry of Indoor Temperature with One Button 50 5 20 Auto Clean Function 50 5 21 WiFi Fu...
Page 6: ...vironment or the place with special requirements such as kitchen Otherwise it will affect the normal operation or shorten the service life of the unit or even cause fire hazard or serious injury As fo...
Page 7: ...lave mode the operation mode of the system is basing on that of the master indoor unit The master indoor unit can be set to any mode including auto mode while the slave indoor unit can t set to the mo...
Page 8: ...ode of the indoor unit conflicts with the system operation mode after voting System mode priority defaults to master slave mode and only certain units have other system mode priorities 3 Display Fig 3...
Page 9: ...of wired controller 3 2 LCD Display Instruction Table 3 1 LCD display instruction No Symbols Instructions 1 Gate control function 2 Child Lock status 3 Slave wired controller address of wired controll...
Page 10: ...HU KIT 9 Indicates that the current system mode priority is voting mode 10 WiFi status If the wired controller has no WiFi function it displays only when the unit connected to G Cloud 11 Timer zone Di...
Page 11: ...ional function 20 I DEMAND function Indoor unit optional function 21 Quiet status including Quiet and Auto Quiet two status 22 Sleep status 23 Left and right swing function 24 Up and down swing functi...
Page 12: ...ys the current type of value In case the wired controller is controlling a Fresh Air Indoor Unit then it will display FAP NOTE When wired controller is connected with different indoor units some funct...
Page 13: ...No 1 2 3 4 Name Panel of wired controller Self tapping screw ST3 9 25 MA Screw M4 25 Soleplate of wired controller QTY 1 4 2 1 4 1 Instruction of wired controller 4 1 1 Requirements for model selecti...
Page 14: ...2 The cord shall be Circular cord the cores shall be twisted together 3 If unit is installed in places with intense magnetic field or strong interference it is necessary to use shielded wire 4 1 2 Re...
Page 15: ...equirements for Wired Connection Network connecting methods between wired controller and indoor unit are as below Fig 4 4 one wired controller Fig 4 5 two wired controllers controls one indoor unit co...
Page 16: ...User Manual 11 Fig 4 6 one wired controller controls multiple VRF indoor units simultaneously Fig 4 7 two wired controllers control multiple VRF indoor units simultaneously...
Page 17: ...User Manual 12 Fig 4 8 one wired controller controls multiple X3 Package indoor units simultaneously Fig 4 9 two wired controller control multiple X3 Package indoor units simultaneously...
Page 18: ...controller s control s multiple indoor units simultaneously the wired controller can connect to any one indoor unit but the connected indoor unit must be the same series indoor unit The total quantit...
Page 19: ...indoor unit s controlled by one wired controller 4 1 4 Installation Fig 4 10 Installation of Wired Controller Fig 4 10 shows a simple installation course of wired controller and the following points s...
Page 20: ...late of wired controller 3 Stick the soleplate of wired controller on the wall and use Self tapping Screw ST3 9 25 MA or screw M4 25 to fix the soleplate with the installation hole of wall 4 Connect t...
Page 21: ...indoor unit in a system other slave indoor units can be set as master unit in which case the original master unit will become a slave unit This function is not applicable to partial units 4 2 2 Parame...
Page 22: ...roject number of online indoor unit Press MODE button in C01 status Press or button to select the project number of indoor unit The current selected indoor unit will beep Temperature zone displays err...
Page 23: ...system C06 View priority operation 00 normal operation 01 priority operation Operation method Enter viewing press MODE button in C06 status to enter the interface of viewing priority operation Press...
Page 24: ...C07 status Press or button to select indoor unit Temperature zone displays current indoor unit project number Timer zone displays indoor ambient temperature C08 View Filter Clean Reminder time 4 416...
Page 25: ...12 View outdoor ambient temperature Timer zone displays outdoor ambient temperature C17 View indoor relative humidity 0 100 relative humidity 0 100 Press MODE button to enter into the review interface...
Page 26: ...ion of one button viewing indoor unit project code Press or button to select the indoor unit Temperature zone displays number of the current indoor unit Timer zone displays project number of indoor un...
Page 27: ...the C18 interface manually the one button viewing function will be immediately turned off 2 If system exits the C18 interface due to no action in 20 seconds user has to press the button under on off...
Page 28: ...mer zone displays air outlet temperature of Fresh Air Indoor Unit NOTE Only applicable to Fresh Air Indoor Unit C23 Version inquiry Timer zone program version of the current wired controller NOTES Und...
Page 29: ...o adjust the parameter value and press ENTER button to finish setting 3 Press ENTER button to return to last step until exists setting parameters The parameter setting list is as following Table 4 2 P...
Page 30: ...01 master wired controller 02 slave wired controller 01 Assistant wired controller 02 is without unit parameter setting function except setting its address P14 Set quantity of group control indoor un...
Page 31: ...fan motor 05 P31 High ceiling installation 00 standard ceiling 01 high ceiling 00 Only applicable to partial cassette units P33 Set Timer 00 general timer 01 clock timer 00 NOTE not applicable to par...
Page 32: ...er auto mode 17 C 30 C 63 F 86 F 25 C 77 F When the temperature unit is C cooling setting temperature minus heating setting temperature 1 C When the temperature unit is F cooling setting temperature m...
Page 33: ...off P46 Clear Filter Clean accumulated time 00 do not clear 01 clear 00 P49 Opening angle of indoor unit air return plate 01 angle 1 25 02 angle 2 30 03 angle 3 35 02 Only applicable to units with air...
Page 34: ...ing the on off status of common indoor unit NOTE only applicable to Fresh Air Indoor Unit P71 Set Setback Function 00 forbidden 01 activated 00 P72 Temperature upper limit for Setback Function 20 30 C...
Page 35: ...atus 00 no 01 yes 01 When it is set as 00 it will keep the status after inserting the gate control card that is if it is OFF status when pulling out the card when inserting the card it is still OFF st...
Page 36: ...hour clock with the AM PM indicator P83 Temperature control method under cooling mode 00 Ambient temperature control 01 Temperature and humidity correction control Depen ding on Indoor unit NOTE Only...
Page 37: ...ormal 02 Quick 03 Deep 01 NOTE Only applicable to the unit with auto clean function P87 Interval of Set temperature in Celsius 00 1 C 01 0 5 C 01 01 The set temperature will be adjusted at 0 5 C 00 Th...
Page 38: ...rfaces of ON OFF status are shown in fig 5 1 5 2 Fig 5 1 Interface of On status Fig 5 2 Interface of Off status 5 2 Mode Setting Under On status pressing MODE button can set mode circularly as OR NOTE...
Page 39: ...F every 0 3s Please refer to 4 2 3 Parameter Setting for the setting method of the temperature setting interval in Celsius In Dry mode when temperature is 16 C or 61 F continuously press button twice...
Page 40: ...r indoor unit code FAP will be displayed as shown below Setting temperature won t be displayed and can t be adjusted via or button The air outlet temperature in cooling or heating can only be set in t...
Page 41: ...e in order to make the room temperature more stable and comfortable 5 5 Timer Setting The wired controller is equipped with two kinds of timer general timer and clock timer General timer is factory de...
Page 42: ...time by 10min hold or button for 10s to increase or decrease clock time by 60min Press ENTER button or TIMER button to save the setting and then exit setting NOTE It is not applicable to partial unit...
Page 43: ...to the setting of unit ON time or unit Off time press ENTER button to cancel timer Press or button to increase or decrease timer time by 1min hold or button for 5s to increase or decrease timer time...
Page 44: ...User Manual 39 Fig 5 3 Unit On Off time setting in unit On status...
Page 45: ...ing 1 When simple swing mode is set in unit on status press SWING button to start or stop up down swing 2 When fixed angle swing mode is set in unit on status press SWING button to adjust swing angle...
Page 46: ...r unit will operate at quiet fan speed Fan speed is lowered so as to reduce the noise of indoor fan motor When Auto Quiet function is enabled indoor unit will change fan speed automatically according...
Page 47: ...ir function is on press FUNCTION button to select Air then press ENTER button to cancel this setting NOTES Air function is only effective for units with air function and fresh air motorized air valve...
Page 48: ...by setting the minimum temperature under Cooling and Dry modes and setting maximum temperature under Heating 3D Heating and Space Heating modes Thus energy saving can be realized Start up Save functio...
Page 49: ...User Manual 44 Fig 5 4 shows how to set Save function for Cooling Fig 5 4 Save Setting for Cooling...
Page 50: ...d buttons for 5s to enter into save setting press ENTER button to cancel Save function of all modes NOTE When the Save function is turned on and then set temperature exceeds the limit value for Save f...
Page 51: ...hin one second to cancel reminding and it will retime according to the original cleaning level 2 Press FUNCTION button to turn to Filter Clean Reminder Function then press ENTER to cancel reminding an...
Page 52: ...s the accumulating operating time is 1400 hours Each time the latter digit increases 1 the operating time increases 400 hours When it reaches 9 it means the operating time is 5000 hours Heavy Pollutio...
Page 53: ...EMAND Setting I DEMAND Function The unit will operate in the SE mode to save energy I DEMAND function can be only be used under cooling mode Under Cooling mode press FUNCTION button to select I DEMAND...
Page 54: ...function will show on the display Pressing and together again for 5 seconds to turn off this function All the other buttons will be disabled when Child Lock function is on 5 18 Gate Control Function W...
Page 55: ...o the instructions as usual after pressing any buttons 5 20 Auto Clean Function In the homepage hold MODE and TIMER buttons for 5 seconds to turn on or turn off Auto Clean function When Auto Clean fun...
Page 56: ...ion cannot be turned on During Auto Clean function is on there will be phenomenon such as frosting of evaporator of indoor unit sound of liquid flow and fluctuation of indoor temperature and humidity...
Page 57: ...Auto Clean mode 5 21 WiFi Function Setting EWPE App can be used to control wired controller Please scan the QR code or search EWPE SMART in the application market to download and install it When EWPE...
Page 58: ...tuation depends on the actual installation For more information please refer to Help in App 5 22 Setback Function In unit off status with Setback Function activated the unit will operate in heating mo...
Page 59: ...ontroller is turned on the wired controller can t enter or exits from Setback Function When the unit is operating at Setback Function the slave wired controller cannot set Save function and doesn t di...
Page 60: ...ction E1 High Pressure Protection JA Protection of Abnormal Pressure E2 Discharge Low Temperature Protection JC Protection of Water Flow Switch E3 Low Pressure Protection JL Protection of Low High pre...
Page 61: ...Heat Exchanger b4 Subcooler Liquid out Temperature Sensor Error F5 Compressor 1 Discharge Temperature Sensor Error b5 Subcooler Gas out Temperature Sensor Error F6 Compressor 2 Discharge Temperature S...
Page 62: ...t Tube Temperature Sensor of Condenser FF Compressor 5 Current Sensor Error bJ High and Low Pressure Sensors are Connected Inversely FJ Compressor 6 Current Sensor Error bP Oil return 2 Temperature Se...
Page 63: ...Power Supply J3 Compressor 3 Over current Protection P3 Protection of Compressor Drive Board Module Reset J4 Compressor 4 Over current Protection H0 Error of Fan Drive Board J5 Compressor 5 Over curre...
Page 64: ...emperature Sensor 2 Error L7 No Master Indoor Unit Error y3 Middle Tube Temperature Sensor 2 Error L8 Power Insufficiency Protection y7 Fresh Air Inflow Temperature Sensor Error L9 Quantity Of Group C...
Page 65: ...r Ld Indoor Fan 2 Error o1 Low Voltage of IDU Bus Bar Ln Lift Panel Return Air Frame Reset Exception o2 High Voltage of IDU Bus Bar d1 Indoor Unit PC Board Error o3 IDU IPM Module Protection d3 Ambien...
Page 66: ...rror of IDU Module dC Capacity DIP Switch Setting Error 6 1 3 Table of Debugging Codes Error Code Content Error Code Content U2 Outdoor Unit Capacity Code Jumper Cap Setting Error C0 Communication bet...
Page 67: ...ication Error UA Overvoltage Protection of DC Bus Bar in Power Grid Side CH Rated capacity is too high UH Under voltage Protection of DC Bus Bar in Power Grid Side CC No master control unit error UC M...
Page 68: ...xchanger and Outdoor Unit Ud Grid connection driver board error Cn Indoor and Outdoor Network Error of Mode Exchanger Un Communication error between grid connection driver board and master controller...
Page 69: ...pressure A9 Operate in Setback Function qE EVI Operating Mode AH Heating qF System compulsory cooling mode AC Cooling qP PV GMV Unit export area setting AF Fan qU Grid voltage system configuration AJ...
Page 70: ...ure Protection P8 Module Temperature Protection U3 DC Bus Voltage Drop Error E2 Freeze Protection U5 Current Detecting Error of Complete Unit L9 High Power Protection PU Capacitor Charging Error U2 Co...
Page 71: ...quid Valve Temperature Sensor Error P9 AC Contactor Protection b7 Gas Valve Temperature Sensor Error PE Temperature Shifting Protection A5 Outdoor Condenser Inlet Pipe Temperature Sensor Error Pd Sens...
Page 72: ...or Fan Non synchronism Protection UL Outdoor Fan Overcurrent Protection EL Emergency Operation Stop A1 Outdoor Fan IPM Module Protection oE Other Error of Compressor C6 Discharge Temperature Sensor Er...
Page 73: ...Sensor Error qE Inverter Indoor Fan Drive Module Temperature Sensor Error E9 IDU Water Full Protection qF Inverter Indoor Fan Drive Storage Chip Error CJ IDU Jumper Cap Error qH Inverter Indoor Fan Dr...
Page 74: ...ers Error q6 Inverter Indoor Fan Out of phase Protection L5 Wired Controller Power Supply Overcurrent Protection q7 Inverter Indoor Fan Drive Module Reset L7 Group controlled IDU Series Inconsistency...
Page 75: ...6 2 3 Table of Status Codes Status Code Content Status Code Content CL Auto clean d1 DRED operation mode 1 Fo Refrigerant recycle mode d2 DRED operation mode 2 H1 Ordinary defrosting status d3 DRED op...
Page 76: ...www argoclima com...