5-17 Diagnostic
With this feature is possible to have a visual signal that a trouble is occurring.
This mode is always active and the signalling is made through the display board LEDS
In case of no troubles the LEDS status follows its normal function.
The detected troubles are showed to the user/technician using the 3 leds of the indoor unit receive
and the 5 leds on the outdoor pcb. For each fault there are different effects upon the operation of the A/C:
NOTES
The troubles are showed according to a priority list that is, in case of more than one
trouble present, is always showed, at first, the one with the highest priority (1
2
3 etc).
Sensor damaged means a situation where sensor is short-circuited or opened
In case of damaged sensors, the system (CM, FMO, FMI etc), if in OFF state, does not start
LD2(opr) LD1(stby) LD3(timer)
4
RAT probe damaged
F
F
O
3
ICT probe damaged
F
O
F
2
communication error
F
F
F
1
fault on outdoor unit
O F
O
0
wrong mode selected
●
F
F
O = LED off
F = LED blinking
●
= LED on
System does not operate. To restart the system,
power re-setting (off-on) is required
The A/C switches off. As soon as fault is
cleared the system automatically restart
LEDS status
system does not operate.To restart the system,
select correct mode
Effects
INDOOR UNIT FAULT
Priority
18
Summary of Contents for FCIBS9
Page 7: ...2 DIMENSIONAL DATA FCIBS9 Units mm 7...
Page 8: ...3 PERFORMANCE DATA 3 1 Air Throw Distance Chart FCIBS9 Floor Mounted Ceiling Mounted 8...
Page 9: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagram 9...
Page 24: ...7 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAYED 7 5 ONLY OUTDOOR UNIT IS OFF 24...
Page 28: ...7 8 NOISE PROBLEM 28...
Page 30: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima com...