5-11 Defrost

The defrost process is controlled by a detection algorithm designed in order to mantain optimal
utilization of the heat pump capacity especially during negative outdoor temperature conditions.

• Compressor speed fixed
• Expansion valve opening fixed 
• Outdoor fan switched off 
• Indoor fan controlled by cold draft prevention
• Defrost valve switched on (open) 
• Reversing valve switched on (heating operation) 

NOTES:
• Minimum defrost time interval is 2 minutes 
• During HIGH POWER operation the defrost detection is ignored until this mode remains active 
• System exits defrost protection as soon as 14°C on the outdoor coil are detected and, in any case,
   if at least 12 minutes are elapsed from the start of the defrost cycle. 

5-12 I FEEL function

As standard configuration  the air conditioner operates detecting the room temperature through the sensor
equipped in the wireless remote controller (icon I FEEL shown on the display). This feature provides a
personalised environment since the temperature can be detected where the remote controller is located.
It is possible to de-activate this option pressing the I FEEL button on the remote controller.
In this case the I FEEL icon is no longer displayed and room temperature is detected through the sensor 
included in the indoor unit.

5-13 HI POWER mode

When this mode is active the internal fan speed is set automatically and the air conditioner operates,
for 15 minutes, at the maximum power. After 15 minutes from the selection the mode is automatically
switched off. 

16

Summary of Contents for FCIBS9

Page 1: ...TECHNICAL DATA SERVICE MANUAL INDOOR UNIT FCIBS9 SPLIT SYSTEM AIR CONDITIONER 0 8180 601 01 09 2012 Model No Product Code No FCIBS9 387005003...

Page 2: ...w wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line...

Page 3: ...off function 17 5 16 Capacity Test Mode 17 5 17 Diagnostic 18 5 18 Indoor unit jumpers Configuration 19 5 19 Outdoor unit jumpers Configuration 19 5 20 Contacts for building automation 19 6 INDOOR UN...

Page 4: ...e mm in Refrigerant Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WIT...

Page 5: ...emp Open C Close Run capacitor F VAC Flap Motor Type Model Rating Coil resistance Ambient temp 25 C Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE 250 V 3 15...

Page 6: ...1 3 Other Component Specifications Thermistor Coil sensor TH1 Resistance Thermistor Room sensor Resistance k 10 3 NTC THERMISTOR 10 at 25 C 6...

Page 7: ...2 DIMENSIONAL DATA FCIBS9 Units mm 7...

Page 8: ...3 PERFORMANCE DATA 3 1 Air Throw Distance Chart FCIBS9 Floor Mounted Ceiling Mounted 8...

Page 9: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagram 9...

Page 10: ...s but in any case The minimum time interval between an OFF and a ON operation is not lower than 3 minutes The minimum operating time is not lower than 3 minutes The maximum acceleration deceleration r...

Page 11: ...The minimum off time of compressor is 3 minutes The indoor fan can change speed only after it has operated at the same speed for 30 sec if in AUTO and 1 sec for the other settings High Med Low 5 3 He...

Page 12: ...two modes is according to the above graph and following table If 3 C Dt 1 C and the compressor is off for more than 1 hour If Dt 3 C and compressor is off for more than 3 minutes If 1 C Dt 3 C and the...

Page 13: ...1 C LEVEL 2 FMO switches 9 minutes off and 3 minutes ON 15 C FMI switches between L and LL every 30 seconds RV off CM off 15 C DRY OFF ZONE FMO off FMI off RV off SPT Set Point Temperature 5 6 Fan Mo...

Page 14: ...coil temperature ICT decreases and acts by decreasing the compresor speed The system exit this protection routine when ICT temperature rises above 5 C 5 9 2 Cold draft This feature prevents the supply...

Page 15: ...built in thermistor is always monitored by the control system and kept operating in a safe area If temperature exceeds 100 C operation is automatically stopped 5 10 4 Outdoor fan power module overhea...

Page 16: ...east 12 minutes are elapsed from the start of the defrost cycle 5 12 I FEEL function As standard configuration the air conditioner operates detecting the room temperature through the sensor equipped i...

Page 17: ...for more than 5 seconds the IFEEL and FAN buttons on the remote controller With this option active the OPERATION TIMER and STANDBY lamps are switched off even during operation they activates only in c...

Page 18: ...more than one trouble present is always showed at first the one with the highest priority 1 2 3 etc Sensor damaged means a situation where sensor is short circuited or opened In case of damaged senso...

Page 19: ...erate always OFF inputs from wireless remote controller are not processed Contact CLOSED system operates in the normal way according to the inputs coming from wireless remote controller INPUT CONTACT...

Page 20: ...emote control unit directly at the air conditioner receiver System starts and runs for 3 minutes After 3 minutes operation in case the setting is right the unit switches to COOL mode and stops set poi...

Page 21: ...er is being supplied WARNING If the following troubleshooting must be done with power supplied be careful not to touch any uninsulated live part that can cause electric shock 7 2 CIRCUIT BREAKER TRIPS...

Page 22: ...e YES Is the unit in protection mode see par 5 9 e 5 10 Wait some minutes to restore normal condition YES NO CASE 1 CASE 2 There is a fault signaling Check outdoor unit leds signaling see par 5 17 Nor...

Page 23: ...he sensor COMMUNICATION ERROR Is the communication fuse blown Replace fuse 100mA The fuse may be not fitted rightly in the fuseholder Check for right connection of communication wires Check outdoor un...

Page 24: ...7 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAYED 7 5 ONLY OUTDOOR UNIT IS OFF 24...

Page 25: ...he fuse may be not fitted rightly in the fuseholder Check for right connection of communication wires Turn off power supply and after 3 minutes turn on again NO See section 7 3 FAULT ON THE INDOOR UNI...

Page 26: ...air filters Check the air filters Are they clogged YES NO Check the expansion valve coil Is it rightly connected and the resistance value correct Replace the expansion valve coil NO There is the possi...

Page 27: ...ES ARE OBSERVED 2 OPERATION DOES NOT SWITCH FROM HEAT TO COOL AND FROM COOL TO HEAT Remote controller unit may be defective Receiver assy may be defective Check the connection of reversing valve coil...

Page 28: ...7 8 NOISE PROBLEM 28...

Page 29: ...isired electric part from terminal plate PCB assy capacitor etc Similary disconnect the connector Then measure the insulation resistance fig 1 to 4 Refer to electric wiring diagram NOTE If the probe c...

Page 30: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima com...

Reviews: