Operation Instructions
22
2.4.14 Current
Limit
[Operation Instructions]
1. At the commissioning parameter setting page, by touching “
Current limit
”, it can be set to “
On
” or “
Off
”.
2. When it is set to “
On
”, it is able to set the limited current value.
3. After that, this setting will be saved by touching the “
Save
” icon.
[Notes]
This setting will be memorized upon power failure.
2.4.15 Address
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Current limit
”, it can be set the address.
[Notes]
It is used to set the address of the control panel for being integrated to the centralized control system.
This setting will be memorized upon power failure.
The setting range is 1~125 and 127~253.
The defaulted address is 1 upon first power-on.
2.4.16 Refrigerant
Recovery
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Refri. recovery
”, it will access to the refrigerant
recovery page.
When “
Refri. recovery
” is set to “
On
”, the control panel will go back to the home page. At this time, any touch
operation except ON/OFF will get no response, with a prompt dialog box popping up, saying “
The refrigerant recovery
is running!
” By touching ON/OFF, refrigerant recovery will quit.
[Notes]
This function is allowed only when the unit has just repowered and not turned on. For the unit which once has
been put into operation, this function is unavailable, alerting “
Wrong operation
”.
This function will not be memorized upon power failure.
2.4.17 Control Logic of the Water Tank Heater
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Tank heater
”, it will access to the setting page of control
logic for the water tank heater.
[Notes]
“Reserved” will be displayed when the water tank is unavailable.