Do not install an air bleeder as this may cause
water to spray from the drain pipe outlet.
(Fig. 3-43)
If it is necessary to increase the height of the
drain pipe, the section directly after the con-
nection port can be raised a maximum of 50
cm. Do not raise it any higher than 50 cm, as
this could result in water leaks. (Fig. 3-44)
Do not install the pipe with an upward gradient
from the connection port. This will cause the
drain water to flow backward and leak when the
unit is not operating. (Fig. 3-45)
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe
should not be allowed to hang unsupported
from its connection to the unit. Fasten the pipe
to a wall, frame, or other support as close to
the unit as possible. (Fig. 3-46)
Provide insulation for any pipes that are
installed indoors.
Fig. 3-43
Fig. 3-45
Fig. 3-44
Air bleeder prohibited
30 cm or less (as short as possible)
50 cm or less
Upward gradient prohibited
Fig. 3-46
Support
pieces
CAUTION
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe,
then secure it with the supplied clamps. (Fig. 3-42)
Make sure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
NOTE
Fig. 3-42
Vinyl clamps
Drain insulator (supplied)