4. Electrical connection 

 

The  electrical  installation  may  only  be  performed  by  qualified  professionals 

(trained  electricians)  with  the  power  off  and  in  accordance  with  the  applicable 

standards  and  guidelines.  The  manufacturer  will  accept  no  responsibility  in  the 

event of improper installation. 

 

4.1. General, plus safety notices 

Comply with national and international guidelines for setting up electrical equipment. 

Power supply in accordance with EN50178, SELV, PELV, VDE0100-410/A1. 

De-energise the system for the installation and connect the device as follows: 

 

Fig. 4.1: Pin assignments for the CAN interface 

The  permissible  operating  voltage  is  between  12V  and  28  VDC.  The  sensor  cable  must  be 

shielded.  Pin  8  und  Pin  9  are  for  the  power  supply  of 

LubMon  Connect

  and  not  for  the  power 

supply of the connected bus devices. 

  Pin 1  --- 

  Pin 2  CAN-L 

  Pin 3  GND 

  Pin 4  --- 

  Pin 5  SHIELD 

  Pin 6  --- 

  Pin 7  CAN-H 

-------- Galvanically isolated -------- 

  Pin 8   (24VDC) 

  Pin 9  supply 

– 

(view of connector from the outside) 

 