p13
PrDI
NAME
«
ON
«
OFF
«
YES
«
NO
1 1 1 1
setting of the brightness of the displays
on 4 levels
not enforced to 0
deleting of the unsignificant zeros
«
ON
«
OFF
mode idle activated after 10 min : automatic
extinguishing of the µconsole display.
«
ABCD
«
NAME
«
SAVE
Name of the programming file
Entering of the programming file name
state of the last digit digit (right hand side)
enforced to 0
Programming of the
brightness, of the display
See also the display features
p18
«
PrDI
«
IDLE
«
NAME
«
LdIG
«
NULL
BRGT
SAVE
SAVE
NO
YES
d D I S
S P I . 1
Exit from the programming with or without saving
exit with
configura-
tion saving
exit without configura-
tion saving
* If on a change of location of the decimal
point (parameter
POIN
) or of operating mode
(parameter
SCALE
) the user has not modified or
validated again the parameters
dDIS , F.DIS ,CUT,
Yxx dODIS, F.OdI
(if option analog) and
SPxx
and
HYSx
(if option relays) then the converter will offer
again after
SAVE YES
all the above named para-
meters which have not been validated again.
revert to
measure
display
*
Note: An exit from mode programming with saving of the configuration (
SAVE,
YES
) will automatically reset to zero the min. and the max., as well as the alarm
recordings.
After
SAVE, YES
la µconsole will show
WAIT
during the converter re-initialisation
phase.
4.5.1 Mode transmitter / indicator
According to the choice
SCALE YES / NO
, you can choose to have or
not to have a physical display on the converter.
SCALE YES
lets the following parameters appear :
POIN
(position of the decimal
point),
dDIS
and
F.DIS
(down and full display scale corresponding to the down
and full input scale, selected in
dINP
and
F.INP
) and
UNIT
(unit of the displayed
physical magnitude) : this unit is recorded in the converter for display on PC
software in association with the physical measure on the setting parameters :
setpoints, hysteresis, etc...
With the configuration
SCALE YES
it may be considered that the converter opera-
tes like an indicator, able to display, either locally (on the µconsole) or in a shif-
ted way with the configuration software, a measured physical magnitude.
Example 1: For a 4/20 mA signal from a level sensor on a tank, the following
programming is displayed :
in the menu
INP: TYPE = mA, FUNC = LIN
,
dINP = 4.00 , F.INP = 20.00
,
in the menu
DISP: SCALE YES, POIN
=
_ _ _ . _
dDIS = 000.0, F.DIS =300.0,
UNIT = LTS
(liters)
CUT = NO
for :
4 mA from the sensor, display =
000.0
-->
000.00 LTS
12 mA from the sensor, display =
150.0
-->
150.00 LTS
20 mA from the sensor, display =
300.0
-->
300.00 LTS
on the µconsole
on the software
4.5 Display of the measure