3. POSSIBLE OUTPUTS
The instrument includes in standard:
-
2 setpoint relay outputs (S5-S6 and S7-S8).
The relay outputs are programmed as alarm setpoint – option R .
Type of contact
: potential free contac, galvanic partition 2.5KV
Rated load
: 5A – 250V
AC
Lifetime
: 20 000 000 operations empty, 300 000 operations at 2A/250V
-
Setpoint outputs:
Setting of the setpoints
: 0 to 100% of the measure range (programmable)
Switching hysteresis
: 0 to 15% of the setpoint (programmable)
Time delay
: 0 to 15s (programmable)
Analog output – option A :
Galvanic partition
: Inputs 2kV, RS485 1kV
Output signal
: programmable (0/20mA or 4/20mA).
Scale setting
: 0 to 100% of the measure range (programmable)
Admissible load
: up to 600
(20mA)
Resolution
: 24000 points
Accuracy
: <0.2% of the full scale on 0/20mA (in relation to the display)
Residual ripple
: -/+2.5mV (dc) on 50
load
Response time of the output
: 50ms (<120ms input
output)
Thermic drifts
: <200ppm caliber 0/20mA