Arctiko ULUF 120 Operating Instructions Manual Download Page 5

5

Warning

Regulations require that this appliance be earthed:
The manufacture declines all liability for injury to persons or animals and for damage to property resulting 

from failure to observe the above procedures and reminders. 

If the socket and plug are not of the same type either the socket or the plug must be replaced by a qualified 

electrician.
Under no circumstances use extension leads or adaptors.

1. The appliance should be connected by an authorised electrician or by the company that sold the 

appliance. Incorrect installation may damage the appliance.

2. Place the appliance on a flat floor that can bear the weight of the appliance.

3. The electrical installation should be earthed.

4. Do not use extension cables. Connect the appliance directly to a fixed installation. If the appliance is 

connected to a long extension cable there is a risk that the cable will become hot.

5. The appliance should be placed in a dry location. Do not allow water to come into contact with the 

cabinet. Water entering electrical parts may cause short-circuiting.

6. In the event of functional or electrical irregularities, please contact an authorised service engineer.

Before Commissioning

Clean the freezer both inside and out using a damp, wrung out cloth. Dry with a dry cloth.
The smell from the plastic parts in the freezer will disappear once the freezer has been cooled down.

Starting procedure

Put the plug in the socket.
The thermostat pre-set by the producer. The appliance should run for at least 6 hours before the thermostat 

is changed to allow for stabilisation of the cooling system.
 

Starting up the freezer

Start the freezer. Set the digital thermometer at the temperature required. It will now take about 

6-10 hours before the set temperature is reached.
The freezer should be cooled down empty.

When filling the unit with racks/boxes, make sure to pre-cool them in order not to effect the inside 

temperature of the unit.

Disconnecting the appliance

Electrical disconnecting must be possible either by unplugging the appliance or by means of a double pole 

switch located up-line from the socket.

Summary of Contents for ULUF 120

Page 1: ...OPERATING INSTRUCTIONS ULUF Models...

Page 2: ...eezer Electrical connection Before commissioning Starting procedure Starting up the freezer Disconnecting the appliance Control Panel Default settings The cooling system CO2 back up Relocating or movi...

Page 3: ...appliance contains a mixture of various refrigerants For more information please refer to the rating plate affixed to the freezer Power Failure The unit is equipped with battery back up for display an...

Page 4: ...ree to the sides at least 15 cm free at the back Electrical connection Trouble free operation this unit must be properly grounded before it is used Failure to ground the equipment may cause personal i...

Page 5: ...w water to come into contact with the cabinet Water entering electrical parts may cause short circuiting 6 In the event of functional or electrical irregularities please contact an authorised service...

Page 6: ...4 5 6 7 8 USB Data download 1 Temperature indicator 2 Alarm indivator 3 Alarm icons 4 Compressor indication 5 Date indication 6 Hour indication 7 Ambient temperature indicator 8 Battery level 9 USB C...

Page 7: ...7 Setting icons Custom Settings Advanced Settings Advanced Service Settings Status Change Reset password Change Reset password Status Advanced Service Settings Advanced Settings Custom Settings...

Page 8: ...arm will occur on the unit and until it will be shown on the display The menu High temp alarm is the settings of the highest temperature the device must be in side before it comes with an alarm The me...

Page 9: ...defrost the deftrost can be started immediately The menu Hysteresis is the setting of the different from the setpoint whwere the compressor will start and stop The menu Temp range limits is the settin...

Page 10: ...splayed Under the menu Probe inside unit the tempe rature of the sensor mounted inside the unit is displayed There is mounted one sensor as stan dard in the unit but it is possible to mount 3 sensors...

Page 11: ...ossible to change the password for Customer Settings Advanced Settings and Advanced Service Settings Under Reset password it is possible to reset the pass word for the Customer Settings Advanced Setti...

Page 12: ...the display USB connected Download Data Place the USB pen drive in the connection on the display and press the button right for read data from the unit to the USB pen The Read data will be shown in t...

Page 13: ...unit The Low temperature alarm indicate that the temperature inside the unit is lower than permitted from setting of the unit The Probe eprom failure alarm indicate that the probe is not working The...

Page 14: ...er 30 Probe eprom failure Freezer 50 Freezer Freezer Enable 14 Default settings ULUF 60 120 400 500 700 800 Description Arctiko default settings Customer settings Advanced Settings Password 0000 Hyste...

Page 15: ...e eprom failure Freezer 90 Freezer Freezer Enable 15 Default settings ULUF 450 450 2M 550 550 2M 750 750 2M 850 850 2M Description Arctiko default settings Customer settings AdvancedSettings Password...

Page 16: ...m Freezer 70 Probe eprom failure Freezer 90 Freezer Freezer Enable 16 Default settings ULUF 15 65 125 Description Arctiko default settings Customer settings AdvancedSettings Password 0000 Hysteresis F...

Page 17: ...m Freezer 70 Probe eprom failure Freezer 100 Freezer Freezer Enable 17 Default settings ULUF 490 590 890 Description Arctiko default settings Customer settings AdvancedSettings Password 0000 Hysteresi...

Page 18: ...from the top of the unit remove kit Make sure that pressurized CO2 escape from the gaskets or pressure valve Relocating or moving the freezer Never leave the freezer to others without instructing thes...

Page 19: ...cabinet and the evaporator system The compressor compartment and in particular the condenser must be kept free from dust and dirt This is best done with a vacuum cleaner and a brush Do not put bottle...

Page 20: ...20 Wiring diagram ULUF 400 450 450 2M 500 550 550 2M 700 750 750 2M PT1000 PT1000 T3 T2 NTC NTC PT1000 100 240V AC 800 850 850 2M...

Page 21: ...21 Wiring diagram for ULUF 15 60 65 120 125 PT1000 PT1000 NTC T3 T2 PT1000...

Page 22: ...22 Wiring diagram for ULUF 490 590 890 T3 T2 PT1000 PT1000 PT1000 100 240V AC...

Page 23: ...23 Notes...

Page 24: ...50 80 038 10 GB WWW ARCTIKO COM LAMMEFJORDSVEJ 5 DK 6715 ESBJERG N DENMARK TEL 45 70 20 03 28 FAX 45 70 20 03 29 INFO ARCTIKO COM WWW ARCTIKO COM...

Reviews: