Arctiko SUF 100 Operating Instructions Manual Download Page 9

9

PARAMETERS

DISPLAY

DEFROST

REGULATION

Hy

Differential:

 (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN is 

Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set point.

LS

Minimum set point:

 (-100°C ÷ SET; [-148F ÷ SET): Sets the minimum value for the set point.

US

Maximum set point:

 (SET÷150°C/ SET÷302°F). Set the maximum value for set point.

Ot

Thermostat probe calibration:

 (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of the 

thermostat probe.

OdS Outputs activation delay at start up:

 (0÷255min) This function is enabled at the initial start up of 

the instrument and inhibits any output activation for the period of time set in the parameter.

AC

Anti-short cycle delay:

 (0÷50 min) minimum interval between the compressor stop and the 

following restart.

CCt Compressor ON time during continuous cycle:

 (0.0÷24.0h; res. 10min) Allows to set the length of 

the continuous cycle: compressor stays on without interruption for the Cct time. Can be used, for 
instance, when the room is filled with new products.

CCS Set point for continuous cycle:

 (-100÷150°C; -148°F ÷ 302°F) it sets the set point used during the 

continuous cycle.

Con Compressor ON time with faulty probe:

 (0÷255 min) time during which the compressor is active in 

case of faulty thermostat probe. With COn=0 compressor is always OFF.

COF Compressor OFF time with faulty probe:

 (0÷255 min) time during which the compressor is OFF in 

case of faulty thermostat probe. With COF=0 compressor is always active.

CH

Type of action:

 CL = cooling; Ht = heating.

CF

Temperature measurement unit

°C

=Celsius; 

°F

=Fahrenheit. WARNING: When the measurement 

unit is changed the SET point and the values of the parameters Hy, LS, US, Ot, ALU and ALL have to 
be checked and modified if necessary).

rES Resolution (for °C):

 (in = 1°C; dE = 0.1 °C) allows decimal point display. 

dLy Display delay:

 (0 ÷20.0m; risul. 10s) when the temperature increases, the display is updated of 1 

°C/1°F after this time.

IdF

Interval between defrost cycles:

 (0÷120h) Determines the time interval between the beginning of 

two defrost cycles.

MdF (Maximum) length for defrost:

 (0÷255min) When

 P2P = n

, (not evaporator probe: timed defrost) it 

sets the defrost duration, when 

P2P = y

 (defrost end based on temperature) it sets the maximum 

length for defrost.

dFd Temperature displayed during defrost:

 (rt = real temperature; it = temperature at defrost start; 

SEt

 

= set point; dEF = 

“dEF”

 label)

dAd MAX display delay after defrost:

 (0÷255min). Sets the maximum time between the end of defrost 

and the restarting of the real room temperature display.

Summary of Contents for SUF 100

Page 1: ...OPERATING INSTRUCTIONS SUF MODELS...

Page 2: ...5 Control panel 6 Main functions 7 How to lock the keyboard 8 Parameters 9 Alarms 10 Alarm relay management 10 Digital input 10 Start defrost 12 Alarm recovery 12 Connections 13 Default setting value...

Page 3: ...s WARNING Keep ventilation openings that are placed in the appliance enclosure or in the built in structure clear of obstruction WARNING Do not use mechanical devices or other means to accelerate the...

Page 4: ...re is too high there is a risk that the freezer will not operate correctly It is recommended that the room is ventilated so that the room temperature does not exceed 77 F at most Class N 3 Place the f...

Page 5: ...l parts it may cause short circuiting 6 In the event of functional or electrical irregularities please contact an authorised servicing engineer Before commissioning Clean the freezer both inside and o...

Page 6: ...emperature display USE OF LEDS Each LED function is described in the following table 1 Press and release the key 2 The Lo message will be displayed followed by the minimum temperature recorded 3 By pr...

Page 7: ...EFROST Push the DEF key for more than 2 seconds and a manual defrost will start HOW TO CHANGE A PARAMETER VALUE To change the parameter s value operate as follows 1 Enter the Programming mode by press...

Page 8: ...sage will be displayed and the keyboard will be locked At this point it will be possible only to see the set point or the MAX o Min temperature stored 3 If a key is pressed more than 3s the POF messag...

Page 9: ...n Compressor ON time with faulty probe 0 255 min time during which the compressor is active in case of faulty thermostat probe With COn 0 compressor is always OFF COF Compressor OFF time with faulty p...

Page 10: ...r failure y the alarm relay is activated if a temperature alarm happens during a power failure n the alarm relay is never activated during a power failure ALF Alarm relay activation for all the alarms...

Page 11: ...1F parameter DOOR SWITCH INPUT i1F dor It signals the door status and the corresponding relay output status through the odc parameter no Fan normal any change CPr F_C Compressor OFF Since the door is...

Page 12: ...unction is enabled until the digital input is activated DIGITAL INPUTS POLARITY The digital input polarity depends on the i1P parameter i1P CL the input is activated by closing the contact i1P OP the...

Page 13: ...13 CONNECTIONS XR30CX 20A COMPRESSOR 12Vac dc supply connect to the terminals 7 and 8 24Vac dc supply connect to the terminals 7 and 8 120Vac supply connect to the terminals 7 and 8...

Page 14: ...14 82 82 95 60 DEFAULT SETTING VALUES...

Page 15: ...te to 02 mbar Evacuation must be performed at two places in the system both from the filling pipe and from the pipe mounted on the pressure side of the compressor Mount the capillary pipe with mountin...

Page 16: ...oose fold which is up is cut off Beware not to damage the rest of the gasket 3 The new gasket with the removed fold is placed on the lid 4 The upper part of the gasket is twisted outwards and the scre...

Page 17: ...side the box and if it is not removed it will cause the lid to open 6 Use authorised cleaning products The use of alcohol dissolvents and alkaline cleaning agents is prohibited 7 Clean the vent holes...

Page 18: ...18 for SUF 100 External alarm Earth connection in compressor compartment External alarm Sensor Battery 6V Sensor Battery Terminal blocks...

Page 19: ...19 for SUF 500 External alarm Earth connection in compressor compartment External alarm Sensor Battery 6V Terminal blocks Sensor Battery Starting relay...

Page 20: ...LAMMEFJORDSVEJ 5 DK 6715 ESBJERG N DENMARK TEL 45 70 20 03 28 FAX 45 70 20 03 29 5080100 04 GB WWW ARCTIKO INT COM WWW ARCTIKO INT COM...

Reviews: