5.4.9 Logical outputs
Logical outputs are used for sending binary signals out from a logic that has been built in the logic
editor. Logical signals can be used for blocking functions, changing setting groups, controlling digital
outputs, activating LEDs, etc. The status of logical outputs can also be reported to a SCADA system.
The figure below presents a logic output example where a signal from the circuit breaker failure
protection function controls the digital output relay number 5 ("OUT5") when the circuit breaker's cart
status is "In". The image above is from the logic editor and the image below from AQtivate 200.
Figure. 5.4.9 - 118. Logic output example.
5.4.10 Logical inputs
Logical inputs are binary signals that a user can control manually to change the behavior of the
AQ-200 unit or to give direct control commands. Logical inputs can be controlled with a virtual switch
built in the mimic and from a SCADA system (IEC 61850, Modbus, IEC 101, etc.). Logical inputs are
volatile signals: their status will always return to "0" when the AQ-200 device is rebooted.
Logical inputs have two modes available: Hold and Pulse. When a logical input which has been set to
"Hold" mode is controlled to "1", the input will switch to status "1" and it stays in that status until it is
given a control command to go to status "0" or until the device is rebooted. When a logical input which
has been set to "Pulse" mode is controlled to "1", the input will switch to status "1" and return back to "0"
after 5 ms.
The figure below presents the operation of a logical input in Hold mode and in Pulse mode.
Figure. 5.4.10 - 119. Operation of logical input in "Hold" and "Pulse" modes.
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
183
Summary of Contents for AQ-S215
Page 1: ...AQ S215 Bay control IED Instruction manual...
Page 249: ...Figure 7 4 151 Example block scheme A AQ Q S215 S215 Instruction manual Version 2 04 248...
Page 269: ...Figure 8 13 172 Device installation A AQ Q S215 S215 Instruction manual Version 2 04 268...
Page 287: ...10 Ordering information A AQ Q S215 S215 Instruction manual Version 2 04 286...