Name
Range
Step
Default
Description
Turnpoint
2
0.01…50.00×I
n
0.01×I
n
3.00×I
n
Setting for second turn point in the bias axe of the differential
characteristics.
Slope 2
0.01…250.00% 0.01%
40.00%
Setting for the second slope of the differential characteristics.
The pick-up settings can be selected via setting groups. The pick-up activation of the function is not
directly equal to the TRIP signal generation of the function. The TRIP signal is allowed if the blocking
condition is not active.
The following figure presents the differential characteristics with default settings.
Figure. 5.3.9 - 61. Differential characteristics for the I0d> function with default settings.
The equations for the differential characteristics are the following:
Figure. 5.3.9 - 62. Differential current (the calculation is based on user-selected inputs and direction).
Figure. 5.3.9 - 63. Bias current (the calculation is based on the user-selected mode).