Inaccuracy:
- Current
- Voltage
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
±1.5 %U
SET
or ±30 mV
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 1.05
→
)
±1.0 % or ±25 ms
IDMT setting parameters:
k Time dial setting for IDMT
A IDMT constant
B IDMT constant
C IDMT constant
0.01…25.00, step 0.01
0…250.0000, step 0.0001
0…5.0000, step 0.0001
0…250.0000, step 0.0001
Inaccuracy:
- IDMT operating time
- IDMT minimum operating time
±1.5 % or ±20 ms
±20 ms
Instant operation time
Start time and instant operation time (trip):
- I
M
/I
SET
ratio 1.05
→
<40 ms
Reset
Reset ratio:
- Current
97 % of the pick-up current setting
Reset time setting
Inaccuracy: Reset time
0.000…150.000 s, step 0.005 s
±1.0 % or ±25 ms
Instant reset time and start-up reset
<45 ms
9.2.1.19 Resistance temperature detectors
Table. 9.2.1.19 - 345. Technical data of the resistance temperature detectors.
Inputs
Resistance input magnitudes
Measured temperatures measured by RTD sensors
Alarm channels
12 individual alarm channels
Settable alarms
24 alarms available (two per each alarm channel)
Pick-up
Alarm setting range
Inaccuracy
Reset ratio
101.00…2000.00 deg, setting step 0.1 deg (either < or > setting)
±3 % of the set pick-up value
97 % of the pick-up setting
Operation
Operating time
Typically <500 ms
9.2.1.20 Arc fault protection (IArc>/I0Arc>; 50Arc/50NArc) (optional)
Table. 9.2.1.20 - 346. Technical data for the arc fault protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Residual current channel I
01
(Coarse)
Residual current channel I
02
(Fine)
Current input magnitudes
Sample-based phase current measurement
Sample-based residual current measurement
A
AQ
Q-F215
-F215