Instruction manual –AQ F210 Feeder Protection IED
252 (292
)
Binary inputs have as standard current consumption of 2 mA when activated and the operating
voltage range is from 0V to 265VAC/DC with software settable activation/release threshold
and 1V resolution. All binary inputs are scanned in 5 ms program cycle and they have software
settable filtering and pick-up delay of input signal and software settable NO/NC selection.
Naming convention of the binary inputs provided by this module is presented in the chapter 6
Construction and installation.
For further details refer to the “Technical data” section of this document.
7.4
D
IGITAL OUTPUT MODULE
DO5
The DO5 module is an add-on module for additional five (5) binary outputs. This module
can be ordered directly as factory installed option or it can be field upgraded if needed after
the first installation of the AQ-200 series IED.
Connector Description
SlotX 1
OUTx + 1 first pole NO
SlotX 2
OUTx + 1 second pole NO
SlotX 3
OUTx + 2 first pole NO
SlotX 4
OUTx + 2 second pole NO
SlotX 5
OUTx + 3 first pole NO
SlotX 6
OUTx + 3 second pole NO
SlotX 7
OUTx + 4 first pole NO
SlotX 8
OUTx + 4 second pole NO
SlotX 9
OUTx + 5 first pole NO
SlotX 10
OUTx + 5 second pole NO
Figure 7.4-6 DO5 Binary output module for five add-on binary outputs.
Properties of this binary input module provided inputs are exactly the same than inputs in the
CPU-module.
Binary outputs control can be settable from the software. As a standard binary outputs are
controlled in 5 ms program cycle. All output contacts are mechanical type. Rated voltage of
the NO/CO outputs is 250VAC/DC.