checked by the receiving part. If VLAN switches are used to build sub-networks the VLAN
Priority and VLAN ID parameters must be set to match with the system specification.
Figure 5-5 Settings for both available GOOSE Publishing datasets.
GOOSE datasets defines the data which will be sent by the GOOSE publisher. Only binary
data and quality information for the binary signals can be sent by the GOOSE publisher.
The binary signals will be mapped to GOOSE input signals on the receiving side together
with the quality information for that binary signal. The quality information in the incoming
frame will be ORed with GOOSE reception timeout supervision information so that quality
information for each GOOSE input can be used in relay logic.
5.1.6
IEC
103
IEC 103 is short for international standard IEC 60870-5-103. Arcteq implements a
secondary station (slave). The IEC 103 protocol can be selected for the available serial
ports of the device. A master or primary station can communicate with the Arcteq device
and receive information by polling from the slave device. Disturbance recordings transfer is
not supported.