Instruction manual –AQ F210 Feeder Protection IED
236 (292
)
5.1.3
M
ODBUS
IO
ModbusIO can be selected for communication on available serial ports. ModbusIO is
actually a ModbusRTU master implementation dedicated for communication with serial
ModbusRTU slaves such as RTD inputs modules. Up to 3 ModbusRTU slaves can be
connected to the same bus polled by the ModbusIO implementation. These are named IO
Module A … IO Module C. Each of the modules can be configured using parameters in the
following table.
Parameter
Range
Description
IO Module[A,B,C] address
[0…247]
Modbus unit address for
the IO Module. 0 = not in
use.
Module[A,B,C] type
[ADAM-4018+]
Type selection for module
Channels in use
[Ch0…Ch7]
Channel selection for the
module.
For each of the 8 channels of the IO module connected thermocouple can be selected.
T.C. type
[+-20mA,Type J, Type K,
Type T, Type E, Type R,
Type S]
Thermocouple
type
setting.
5.1.4
IEC
61850
Device models with IEC 61850 support, can have the IEC 61850 protocol enabled by the
user. IEC 61850 in Arcteq devices support the following services:
Dataset, pre-defined datasets can be edited with IEC 61850 editor tool in Aqtivate.
Report control block, both buffered and un-buffered reporting is supported.
Control, ‘direct-with-normal-security’ control sequences are supported.
GOOSE
Time synchronization