Instruction manual – AQ 110 arc protection unit
27 (80
)
Figure 4.5 AQ 08 arc light fiber optic loop sensor
Note: On request AQ 08 ends can be covered with black rubber part for any
requested portion to avoid light detection outside the protected zone. For more
information consult your nearest Arcteq representative.
4.4.1
AQ
08
T
ECHNICAL DATA
Light intensity threshold
8000Lux
Detection radius
360 degrees
Maximum length
40 meters
Diameter
1.2 millimeters
Bending radius
1 centimeter
Operating temperature
-40...+125 C