Instruction manual – AQ 110 arc protection unit
28 (80
)
4.5
S
ENSOR
T
YPE
D
EPENDENCIES
Different sensor types can be utilized in different arc flash protection units of
the AQ 100 series. The table below describes the dependencies.
Table 4-1: Arc sensor dependencies
AQ 01
AQ06
AQ07
AQ08
AQ101
Yes
Yes (with fiber option)
Yes (with fiber option)
Yes (with fiber option)
AQ102
No
Yes
Yes
Yes
AQ110P
Yes
Yes (with fiber option)
Yes (with fiber option)
Yes (with fiber option)
AQ110F
No
Yes
Yes
Yes
4.6
S
ENSOR
C
ONNECTION
4.6.1
A
RC LIGHT POINT SENSOR
AQ01
CONNECTION
1) Open the sensor side-covers, then detach the pluggable connectors from the
sensor PCB, and prepare the twisted shielded pair cable connecting. (See Figure
4.6)
Figure 4.6