Radiated (EN 55011, class A)
30…1,000 MHz
Immunity
Electrostatic discharge (IEC 244-22-2 and EN 61000-4-2, level 4)
Air discharge: 15 kV
Contact discharge: 8 kV
Electrical fast transients (EN 61000-4-4, class III & IEC 801-4, level 4)
Power supply input: 4 kV, 5/50 ns
Other inputs and outputs: 4 kV, 5/50 ns
Surge (EN 61000-4-5, level 4)
Between wires: 2 kV, 1.2/50 µs
Between wire and earth: 4 kV, 1.2/50 µs
RF electromagnetic field (EN 61000-4-3, level 3)
f = 80…1,000 MHz, 10 V/m
Conducted RF field (EN 61000-4-6, level 3)
f = 150 kHz…80 MHz, 10 V
11.7. Voltage tests
Insulation test voltage (IEC 60255-5)
2 kV, 50 Hz, 1 min
Impulse test voltage (IEC 60255-5)
5 kV, 1.2/50 µs, 0.5 J
11.8. Mechanical tests
Vibration test
2…13.2 Hz (± 3.5 mm)
13.2…100 Hz (±1.0 g)
Shock/bump test (IEC 60255-21-2)
20 g, 1,000 bumps/dir.
11.9. Environmental conditions
Specified ambient service temperature
–35…+70 ºC
Transportation and storage temperature
–40…+70 ºC
Relative humidity
Up to 97 %
Altitude
Up to 2,000 m above sea level
11.10. Casing and packaging
Protection:
- front
- back
IP 52
IP 20
Dimensions (W × H × D):
- device
- package
102 × 177 × 162 mm
230 × 120 × 210 mm
Weight
1.2 kg
1.5 kg (with package)
A
AQ
Q-103L
-103LV
V
Instruction manual
Version: 1.00
41
© Arcteq Relays Ltd