DS2/DS4 Hardware Manual
Page 42
4-Wire Transmitter, Self-Powered
Some HART devices are separately powered and provide power on the HART loop without requiring an
external supply. A typical wiring arrangement is shown below.
CHx +
CHx -
HART
HART Signal -
250
Ω
Up to 15 HART Devices in
Multidrop mode, or 1 Device in
Point-to-point mode
Power +
Power -
HART
HART Signal -
Power +
Power -
4-Wire Self Powered
HART Transmitter(s)
AIM104-HBI
2-Wire Valve Positioner
+24F
CHx +
CHx -
IOUTx
FGND
Loop 24 V PSU
- +
250
Ω
Signal -
2-Wire HART
Valve Positioner
AIM104-HBI