ATTENTION! :
To carry out the electrical connections
to the
T–MB
control,remove the insulated protection
device from the clamp. Once the electrical connections
are completed, replace the protection device, as in
Fig. 2.
Reassemble the front part of the control, placing
the two flaps located on the lower side and then
close the control, by making the upper flap click
.
CONTROL WIRING CONNECTIONS
The control panel must be wired to the power board
located inside the electrical compartment of the unit,
complying with the correspondence of the common
numbering to both boards.
Use 3 conductors with 0,5 mm2 section.
NOTE:
The connection wirings must not exceed 20
metres in length.
RESPECT THE RIGHT WIRING SEQUENCES
SETTING DIP SWITCHES
Set
DIP
can be used to modify the functions performed
by the controller (as shown in the table below).
1
2
OFF
OFF
Not
used
ON
DIP
DEFAULT
OFF
POSIZIONE
3
4
ON
ON
Not
used
Select the temperature sensor
fitted on the appliance
Select the temperature sensor
fitted on the
T–MB
AU Configuration
AIR CURTAIN
Configuration
Dip dedicated to manufacturer
AIR CURTAIN and AU
Configuration
MB Configuration
ENABLE ROOM AIR TEMPERATURE PROBE
- DIP Nr. 2 -
In particular,
DIP NR. 2
defines which room probe must
be used.
In fact, an air probe (T1 probe) is installed on the intake
of the cassette and fancoil devices.
The
T–MB
control is also equipped with air probe.
- DIP nr. 2 OFF
The inside T-MB sensor is activate;
- DIP nr. 2 ON
The T1 probe, connected to the device main board
(intake air probe) is activated.
1
2
3
Fig. 2
5
6
7
5
6
7
SELV Board
T-MB
OFF
ON
1
2
3
4
1
2
3
3
4
OFF
OFF
MASTER
SLAVE
Use with
T-MB control
ON
DIP
DEFAULT
OFF
POSITION
5
6
OFF
OFF
ASYNCHRONOUS
MOTOR
ECM
MOTOR
Use with
infra-red control
Operation mode with
ELECTRICAL RESISTANCE
Operation mode with
On / Off valve
Dip dedicated to manufacturer
-
SETTING DIP SWITCHES N. 3
DIP N. 3 = ON
ON