7.2.2
Logging Time
4. Press the LOGGING TIME soft key to define the time period to
log data when a trigger becomes active. There are two values to
set: MaxLogTime and PostFault (time). MaxLogTime defines the
number of seconds to record data during which the specific trigger is
active (i.e. faulted). PostFault time defines the number of seconds
that the 933A records data after the trigger becomes inactive (i.e.
after the fault has disappeared).
Figure 7.4: Configuring
Data Logging Times
5. Press the BACK soft key to return to the previous (Edit User
Trigger) screen.
7.2.3
Back Soft key
6. Press the BACK soft key to return to the trigger summary screen
and view any of the trigger settings by trigger number.
Figure 7.5: User Trigger
View
104