10
Arad Technologies Ltd.
|
st.
HaMada, Yokneam Elite , 2069206, Israel
|
w w w . a r a d . c o . i l
4.6
Update Mode – Sonata period time for send data to Encoder module:
4.6.1
Period – every predefined time (in Minutes” field,
) Sonata shall send data to
Encoder module. (1…59 minutes. Default 5 minutes)
4.6.2
Once – fixed time when Sonata shall send data to Encoder module once a day (
). Field “First” shall contain time in format: hours and minutes.
4.6.3
Twice - fixed time when Sonata shall send data to Encoder module twice a day (
). Fields “First” and “Second” shall contain time in format: hours and minutes.
4.7
AMR Serial Number – up to 8 digits ID number (default same as meter ID)
•
Only numeric numbers (in backwards mode).
•
Only 8 least significant numbers (in backwards mode).
4.8
Number of digits - 1- 8 digits from the right most position to be sent to the 2/3W reader
(default 8 digits).
4.9
TPOR - Time that the reader waits until the master stops the start sync (see
) (0…1000ms. Default 500ms).
4.10
2W Pulse Width – (60…1200ms. Default 800ms).
4.11
Units – flow units and volume units the same as in Sonata water meter (read only).
4.12
Encoder module doesn’t support alarms in backward format. Therefore we can’t have
option for Alarms indication on module side.