![AquatiControl Technology ELC-800r Operation And Maintenance Manual Download Page 6](http://html1.mh-extra.com/html/aquaticontrol-technology/elc-800r/elc-800r_operation-and-maintenance-manual_2961882006.webp)
ACT 2009
- 6 -
Wiring Diagram
Input/Output Terminal
1 2 3 4 5 6 7 8 9 10
11
12
13
14
15
Fill Valv
e Ground
Fill Valv
e 2
4
VAC
Fill Valv
e 2
4
VAC
Ground
24VAC
24VAC
Relay Common
Relay Normally Open
Relay Normally Closed
Normal Level Sensor – Black Wire
Normal Level Sensor – Green Wire
Normal Level Sensor – Red Wire
Low Level Sensor – Black Wire
Low Level Sensor – Green Wire
Low Level Sensor – Red Wire
Single Level Control
Normal Level Sensor attaches to normal level sensor terminals (#’s 10,11,12) & Fill
Valve attaches to fill valve terminals (#’s 1,2,3).
Dual Level Control
Normal Level Sensor attaches to normal level sensor terminals (#’s 10,11,12) & Fill
Valve attaches to fill valve terminals (#’s 1,2,3). Low Level Sensor attaches to low level
sensor terminals (#’s 13,14,15).
•
Low Water Pump Cut Off
– 24VAC (#5) to pump contactor (supplied by
others), 24VAC (#6) jump to Relay Common (#7), & Relay Normally Closed (#9)
to pump contactor (supplied by others).
•
Low Water Alarm
– 24VAC (#5) to 24VAC Alarm, Light or Sounder (supplied
by others), 24VAC (#6) jump to Relay Common (#7), & Relay Normally Open
(#8) to 24VAC Alarm, Light or Sounder (supplied by others).