AquatiControl Technology ELC-800r Operation And Maintenance Manual Download Page 1

 
 
 
 

 

O

PERATION AND 

M

AINTENANCE 

M

ANUAL

 

 

ELC-800r 

A

UTOMATIC 

W

ATER 

L

EVEL 

C

ONTROLLER

 

 

 

 
 
 

AquatiControl Technology 

 

3820 South Federal Blvd. 

Sheridan, Colorado   80110 

Toll Free:  877.755.8817 

Fax:  303.761.1499 

www.aquaticontrol.com

 

 
 

 

Serial No. _____________________  

       Model No. _______________________

Summary of Contents for ELC-800r

Page 1: ...800r AUTOMATIC WATER LEVEL CONTROLLER AquatiControl Technology 3820 South Federal Blvd Sheridan Colorado 80110 Toll Free 877 755 8817 Fax 303 761 1499 www aquaticontrol com Serial No _________________...

Page 2: ...ACT 2009 2 TABLE OF CONTENTS Introduction 3 Installation 4 5 Wiring Diagram 6 Operation 7 8 Routine Maintenance 9 Troubleshooting 10 11 Warranty 12...

Page 3: ...is manual Line drawings for each sensing configuration can be found on our website at www aquaticontrol com The ELC 800r should ship with the following contents 1 Control unit 1 Sensing Unit Standard...

Page 4: ...ol The normal water level should sit approximately 1 from the bottom of the end cap The surge tank sensing unit is installed in the surge tank at normal operating water level with the included clic co...

Page 5: ...r setting to shut off a circulation pump in a low water situation A 24VAC contactor in line with the pump is needed and not supplied Also required is another sensing unit that will suit the needs of t...

Page 6: ...mal level sensor terminals s 10 11 12 Fill Valve attaches to fill valve terminals s 1 2 3 Dual Level Control Normal Level Sensor attaches to normal level sensor terminals s 10 11 12 Fill Valve attache...

Page 7: ...olenoid opening Fill on delay can be set from 15 seconds to 99 seconds DEFAULT 15 seconds MAX FILL TIME maximum time solenoid valve is allowed to stay on per fill cycle Max fill time can be set from 2...

Page 8: ...RESET PASSWORD enables password protection of settings NONE No password required to change settings NEW Enter up to 8 digit 0 9 password If the password is forgotten the user can perform a master res...

Page 9: ...t normally need to be cleaned SURGE TANK The Surge Tank Sensing Unit will not normally need to be cleaned however if the cap on the bottom of the sensing application becomes clogged with debris it can...

Page 10: ...hut off Turn on valve Defective sensor Replace sensor Sensing unit not set properly Readjust sensor to desired water level Wiring is incorrect in sensor junction box Check wiring connection Level ligh...

Page 11: ...RECTIVE ACTION Can not change settings Forgotten wrong password Reset ELC by turning the power on while holding the up and down arrows ELC does not allow pump to turn on ELC is still in alarm and need...

Page 12: ...or part which is returned transportation prepaid to the factory within one year of delivery to the original purchaser and which is proven defective upon examination ACT disclaims all liability for da...

Reviews: