Environmental Monitoring System (EMS-5X, 10X and OS) Instruction Manual
33
4.2.7
Relay Settings
The unit has
16 output relays
(section
). Relays 11, 12, 13, 15, and 16 are
dedicated to specific functions and
cannot be changed
. Functions of remaining relays (1-10 and
14) are configurable.
The
RelaySettings
attribute folder contains element settings to configure relays and relay alarms:
Figure 25:
Expanded RelaySettings
,
Relay, Triggers and Trigger Folders
A.
Relay 14 Configuration
Relay 14 Setting
Description
Relay14Function
Relay 14. Set to respond to
alarm
,
cablebreak
, or
either
. Text must be
lowercase
. The relay will reset as soon as faults or alarms have been cleared
).
Table 12:
Relay 14 Settings
Configure relay 14 as follows:
1.
Click the icon next to the
RelaySettings
attribute folder to expand it. The
Relay14Function
element will appear
below, along with its
element
text to
change
in the right column (
2.
Click the Relay14Function
element
text to
change
to highlight
and edit as required
3.
Once editing of the file is complete, update
the
configuration version
,
date
, and
author
. Use the XML or text editor
‘Save
As’ option to rename the file to the
updated version number.
Relays can be triggered
by one or more station
zones and sensors.
Attribute
Folder
Element text to change
Relay
profile
Trigger
Folder
Triggers
profile